Checking The Protective Devices - Sanyo KH2442 / CH2442 Service Manual

Split system air conditioner
Hide thumbs Also See for KH2442 / CH2442:
Table of Contents

Advertisement

(2)

Checking the Protective Devices

Disconnect the connector, which consists of P (plug) and S (socket) when you want to
check the protective device.
Then check continuity among plug's (and/or socket's) terminal as in Fig. IV-18.
Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.
1 1 1 1 1
Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
Disconnect the connector which leads to the indoor fan motor (FMI).
Check the socket's terminals.
2 2 2 2 2
Compressor motor thermal protector . . . . . . Outdoor unit
Disconnect the wires from terminals of compressor.
Check the terminals of compressor.
3 3 3 3 3
Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
Disconnect both the connector which leads to the outdoor fan motor (FMO).
Check socket's terminal.
socket
Multimeter
0642_X_S
IV - 31
4. Service procedures
Fig. IV-18
Section
1
2
3
4
SM830082
SM830082