2-4 Outdoor Fan Control
• In low outdoor temperature, the outdoor fan is set automatically from HIGH to LOW to
prevent the indoor heat exchanger from freezing.
• When the outdoor temperature falls below 25.5°C, the outdoor fan is set from HIGH to
LOW automatically. When the outdoor temperature rises to 27.5°C, the outdoor fan is
set from LOW to HIGH automatically.