6. Electric Heating Function of Chassis
(1) When T
≤0ºC, the electric heating of chassis will operate;
outdoor amb.
(2) When T
>2ºC, the electric heating of chassis will stop operation;
outdoor amb.
(3)When 0ºC<T
outdoor amb.
7. Electric Heating Function of Compressor
(1) When T
≤-5ºC, compressor stops operation, while the electric heating of compressor starts operation;
outdoor amb.
(2) When T
>-2ºC, the electric heating of compressor stops operation;
outdoor amb.
(3) When -5ºC<T
outdoor amb.
44
28
≤2ºC, the electric heating of chassis will keep original status.
≤-2ºC, the electric heating of compressor will keep original status.