Operation - Macurco CD-12 User Instructions

Carbon dioxide detector, controller and transducer
Table of Contents

Advertisement

Available languages

Available languages

Operation

1.
With the display function turned "On", the CD-12 will show the current concentration of CO2 ppm in the air. Normal outdoor
concentration ranges between 350-450 ppm. When the CO2 concentration reaches the Fan Relay setting (1000ppm, for
example) the display will flash back and forth between "FAn" and "1000". With the display function turned "Off", the display
does not show the CO2 concentration, but will show "FAn" as long as the fan relay is activated.
2.
With the display function turned "On" and the CO2 concentration reaching the Alarm Relay setting, (2000 ppm, for example) the
display will flash back and forth between "ALr" and "2000". The buzzer will sound indicating "Alarm" if the buzzer is turned "On".
With the display function turned off the display does not show the CO2 concentration, but will show "ALr" when the Alarm relay
is activated.
3.
With the 4-20 mA function turned "On" and the CO2 concentration climbing, the 4-20 mA signal will ramp up corresponding to
the concentration (0-2000 ppm, for example). The display will show "FAn" and "ALr" and sound as outlined above.
Default Configuration – Factory Settings
The default Power Up Test setting is On
The default Display setting is On
The default Buzzer setting is On
The default Alarm Relay Setting is activation at 2000 ppm
The default Alarm Relay Configuration setting is Normally Open
The default Fan Relay Setting is activation at 1000 ppm
The default Fan Relay Delay setting is 3 minutes
The default Fan Relay Minimum Runtime setting is 0 minutes
The default Fan Relay Latching condition is OFF
The default Trouble Fan Setting condition is OFF
The default 4-20mA Output setting is On
To change settings, remove the Philips screw on the front of the CD-12. Pull off the front cover of the unit.
13

Advertisement

Table of Contents
loading

Table of Contents