Carrier 40MPHA Service Manual page 37

High wall unit ductless system
Hide thumbs Also See for 40MPHA:
Table of Contents

Advertisement

E4/E5/F1/F2/F3 (Open circuit or short circuit of temperature sensor diagnosis and solution)
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure.
Recommended parts to prepare:
Wiring mistake
Faulty sensor
Faulty PCB
Troubleshooting and Repair:
Check the connection between
temperature sensor and PCB.
Is it properly wired ?
Measure the resistance value
of the sensor.
Is it within acceptable
parameters?
Replace indoor or outdoor PCB.
40MPHA-03SM
YES
YES
Fig. 23 —Multimeter
Specifications subject to change without notice.
NO
Ensure proper connections .
NO
Replace the sensor.
37