Appendix
Power supply:
Is the phase sequence of L1, L2, L3, N and PE in the outdoor unit correct?
Is the phase sequence of L1, L2, L3, N and PE in the indoor unit correct?
Does the power supply correspond to the installation instructions?
Fuse for outdoor unit and electric booster heater, tripping characteristics?
Manual operation:
Was a function check of individual component groups performed
(pump, mixing valve, diverter valve, compressor, etc.)?
Comments:
Have the temperatures in the menu been checked and documented?
T0
T1
TW1
TC0
TC1
Settings for auxiliary heater:
Time delay, booster heater, target setting 0 min
Block auxiliary heater
Electric booster heater connected load settings
Auxiliary heater, maximum temperature
Safety functions:
Block outdoor unit at low outside temperatures
Has the commissioning been performed correctly?
Does the installer have to perform additional measures?
Comments:
Installer signature:
Customer or installer signature:
Table 9 System commissioning report
36
 Yes |  No
 Yes |  No
 Yes |  No
 Yes |  No
 Yes |  No
________ °C
________ °C
________ °C
________ °C
________ °C
 Yes |  No
________ °C
 Yes |  No
 Yes |  No
Compress Hybrid 7000i AW – 6721833053 (2020/09)