Section 5
4x Registers
DPU2000R
DPU 2000R
register addr.
description
41409
Data Control
1=First record;
2=Next record;
3=Oldest
Unreported record
41410
Fault type element
41411
Active set and recl.
Seq.
41412
Fault number
41413
Year
41414
Month
41415
Day
41416
Hours
41417
Minutes
41418
Seconds
41419
Hundredths of
Seconds
41420
Ia (Scale at
register 41424)
41421
Ib (Scale at
register 41424)
41422
Ic (Scale at register
41424)
41423
In (Scale at
register 41424)
41424
Current ( I ) Scale x
41425
Ia Angle
41426
Ib Angle
41427
Ic Angle
41428
In Angle
41429
Zero Seq I (Mag)
41430
Pos Seq I (Mag)
41431
Neg Seq I (Mag)
41432
Zero Seq I (Ang)
41433
Pos Seq I (Ang)
41434
Neg Seq I (Ang)
46
Table 20:
Mitigation of Modbus mapping for fault records block
REF615R
Scale
register
Scale
addr.
1
41409
1
1
41410
1
1
41463
1
41464
1
1
41412
1
1
41413
1
1
41414
1
1
41415
1
1
41416
1
1
41417
1
1
41418
1
1
41419
1
1
41420
100
1
41421
100
1
41422
100
1
41423
100
1
41424
1
1
1
1
1
1
1
41430
100
1
41431
100
1
1
1
IEC 61850 path
LD0.FLTMSTA1.ProFcn.stVal
LD0.FLTMSTA1.ActSG.stVal
LD0.FLTMSTA1.ShotPntr.stVal
LD0.FLTMSTA1.AmpsA.mag.f
LD0.FLTMSTA1.AmpsB.mag.f
LD0.FLTMSTA1.AmpsC.mag.f
LD0.FLTMSTA1.AmpsN.mag.f
LD0.FLTMSTA1.AmpsPsSeq.mag.f
LD0.FLTMSTA1.AmpsNgSeq.mag.f
DPU2000R Modbus Point List Mitigation Manual
1MRS240173-IB B
Comments on REF615R
Modbus points mapping
Data Control 1=First record;
2=Next record; 3=Oldest
Unreported record
Protection function, see table
7.1 from "Feeder Protection
and Control REF615R Modbus
Point List Manual"
(1MRS240052-IB)
Active setting group
Auto reclosing shot pointer
value Au
Fault number after device
powers up, it does not count
fault records saved before
power up.
Year
Month
Day
Hours
Minutes
Seconds
Hundredths of Seconds
reading per unit value by
default
reading per unit value by
default
reading per unit value by
default
reading per unit value by
default
100 by default
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R
N/A in REF615R