Rms Demand Current/Real And Reactive Power Values Block; Table 13. Mitigation Of Modbus Mappings For Rms Demand Current/Real And Reactive Power Values Block - ABB Relion REF615R Manual

Modbus point list mitigation
Hide thumbs Also See for Relion REF615R:
Table of Contents

Advertisement

Section 5
4x Registers
DPU2000R
register
DPU 2000R description
addr.
40339
Fault Distance
40340-341
Vbus to Vline Voltage
Difference
40342
Vbus to Vline Angle
Difference
40343
Sync Check Slip
Frequency
40344-345
Zero Sequence
Voltage Mag (Derived)
40346
Zero Sequence
Voltage Ang (Derived)
40347
substation battery
(Vdc)
5.1.4
DPU2000R
DPU2000R
register
description
addr.
40385
Demand Current-A
40386
Demand Current-B
40387
Demand Current-C
40388
Demand Current-N
40389-390
Demand kWatts-A
40391-392
Demand kWatts-B
40393-394
Demand kWatts-C
40395-396
3 Phase Demand
kWatts
40397-398
Demand kVARs-A
40399-400
Demand kVARs-B
40401-402
Demand kVARs-C
40403-404
3 Phase Demand
kVARs
36
REF615R
Scale
register
addr.
1
40339
1
40340-341
1
40342
1
40343
1
1
1

RMS Demand Current/Real and Reactive Power Values Block

REF615R maps all the registers in this block in the same way as in DPU2000R except
some scaling factor difference. Please see Section 5.1.3 on how to change the default
scaling factors.
Table 13:
Mitigation of Modbus mappings for RMS demand current/real and reactive power values block
REF615R
Scale
Scale
register addr.
1
40385
100
1
40386
100
1
40387
100
1
40388
100
1
40389-390
1
1
40391-392
1
1
40393-394
1
1
40395-396
1
1
40397-398
1
1
40399-400
1
1
40401-402
1
1
40403-404
1
Scale
IEC 61850 path
1
LD0.DRFLO1.FltDisKm.mag.f
100
LD0.SECRSYN1.DifVClc.mag.f
1
LD0.SECRSYN1.DifAngClc.mag.f
1000
LD0.SECRSYN1.DifHzClc.mag.f
IEC61850 path
LD0.CMSTA1.AvAmpsA.mag.f
LD0.CMSTA1.AvAmpsB.mag.f
LD0.CMSTA1.AvAmpsC.mag.f
LD0.RESCMSTA1.AvAmps.mag.f
LD0.SPEMSTA1.AvWPhsA.mag.f
LD0.SPEMSTA1.AvWPhsB.mag.f
LD0.SPEMSTA1.AvWPhsC.mag.f
LD0.PEMSTA1.AvW.mag.f
LD0.SPEMSTA1.AvVArPhsA.mag.f
LD0.SPEMSTA1.AvVArPhsB.mag.f
LD0.SPEMSTA1.AvVArPhsC.mag.f
LD0.PEMSTA1.AvVAr.mag.f
1MRS240173-IB B
Comments on
REF615R Modbus
points mapping
reading per unit value
by default
N/A in REF615R
N/A in REF615R
N/A in REF615R
Comments on REF615R
Modbus points mapping
reading per unit value by
default
reading per unit value by
default
reading per unit value by
default
reading per unit value by
default
DPU2000R Modbus Point List Mitigation Manual