1MRS240173-IB B
DPU2000R
DPU 2000R
register
description
addr.
41201:6
OUT5
41201:5
OUT4
41201:4
OUT3
41201:3
OUT2
41201:2
OUT1
41201:1
Close(reserved)
41201:0
Trip
5.3
5.3.1
REF615R
DPU2000R Modbus Point List Mitigation Manual
REF615R
register
IEC 61850 path
addr.
41207:8
LD0.XUGGIO100.SPCSO5.Oper.ctlVal
41212:8
LD0.XBUGGIO100.SPCSO5.Oper.ctlVal
41207:6
LD0.XUGGIO100.SPCSO4.Oper.ctlVal
41212:6
LD0.XBUGGIO100.SPCSO4.Oper.ctlVal
41207:4
LD0.XUGGIO100.SPCSO3.Oper.ctlVal
41212:4
LD0.XBUGGIO100.SPCSO3.Oper.ctlVal
41207:2
LD0.XUGGIO110.SPCSO2.Oper.ctlVal
41212:2
LD0.XBUGGIO110.SPCSO2.Oper.ctlVal
41207:0
LD0.XUGGIO110.SPCSO1.Oper.ctlVal
41212:0
LD0.XBUGGIO110.SPCSO1.Oper.ctlVal
41207:12
LD0.XUGGIO100.SPCSO1.Oper.ctlVal
41212:12
LD0.XBUGGIO100.SPCSO1.Oper.ctlVal
Modbus client controlling physical contacts only works when the
REF615R protection relay is set at both remote and test mode.
Totally there are 15 control blocks in REF615R. Please check "REF615R Modbus
Communication Protocol Manual", Document ID: 1MRS240047-IB, section 3.3.6 for
more details on how to use control blocks. REF615R has added several control commands
which are not available in DPU2000R. To find out entire REF615R control commands,
please check "Feeder Protection and Control REF615R Modbus Point List Manual"
document ID: 1MRS240052-IB, the table of Control Structures.

Function code 23 (Read/write 4x registers)

Fault Record

REF615R maps the fault records format and contents as close as possible to those in
DPU2000R.
Section 5
4x Registers
Comments on REF615R Modbus points
mapping
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
Normal speed BIO card, need to set relay in
test mode and remote mode
High speed BIO card, need to set relay in
test mode and remote mode
45