Honeywell GENT COMPACT-MAINS-DAU Commissioning Instructions page 25

Mains powered dau
Table of Contents

Advertisement

q
Any of the 3 monitored Inputs (MI/Ps) can be enabled by deselecting the respective checkbox.
Normally the box is checked to signify the respective Monitored Input is not used and is disabled. For
each enabled monitored input select either EOL monitoring or Logic level input. The EOL monitoring
method allow wiring to external equipment to be monitored for open or short circuit fault. Each
monitored input relate to the respective a device channel, for example MI/P 1 to MI/P 3 relates to Main
Powered DAU Device Channels 1 to 3. Each device channel can be configured to trigger a command
build action in the Vigilon Compact VA system, see Commissioning tool manual for details
r
"
It is recommended that the volume level of VA remain set at maximum level 0dBA, this is to ensure the alarm
sound can be heard in all areas.
s
Once the Mains Powered DAU is fully configured select the Save button and then move on and configure the next Mains Powered
DAU on the loop. On completion of all configuration work transmit the configuration to the panel and backup the configuration at the
panel.
www.acornfiresecurity.com
End-of-Line (EOL) Monitoring
External Equipment
W
10K Resistor
W
10K Resistor
Switch closed: Normal
Switch open: triggered
M3+
M3-
M1+
M1- M2+ M2-
MI/P3
MI/P1
MI/P 2
PB14
PB12
PB13
CONTROL BOARD
Mains DAU
The volume levels of voice alarm, public address and background music can be
preset. As default the VA and PA are set to maximum and background music is set
at -15dB. A customer may want the volume levels to be adjusted for each audio. For
example the background music volume level will need to be set at a higher level in
areas where there is noise, such as in a workshop. On the
other hand in an office environment the volume level will need to be lower.
On selecting a sector in the system tree you can configure the sector attention-tones and
messages associated with Sector signals 0, 1, 2 and 3. The default tone and message
for each signal is marked with an asterisk * and those which are non compliant are
marked with an exclamation !. The duration of silence gaps before and after a message
can be set to site requirements. The exception is the gap for Evacuate messages which
is fixed to meet the requirements of standards and therefore cannot be adjusted.
A 'Play out Message' feature can be enabled by a check box which allows an audio
message to finish properly and therefore prevent an abrupt ending of an announcement.
www.acornfiresecurity.com
Mains Powered DAU
Logic Level Input
External Equipment
Switch open: Normal
Switch closed: triggered
M3+
M3-
M1+
M1- M2+ M2-
MI/P3
MI/P1
MI/P 2
PB14
PB12
PB13
CONTROL BOARD
Mains DAU
25