Indicators, Fuses And Link On The Psu Board - Honeywell GENT COMPACT-MAINS-DAU Commissioning Instructions

Mains powered dau
Table of Contents

Advertisement

Commissioning instructions

Indicators, fuses and link on the PSU board

Mains supply fuse
FS3 3.15A(T)
or
43V supply fuse
FS6 - 1.6A
Y1
Y2
-
-
-
fast flash
amber
-
slow flash
amber
-
slow flash
amber
fast flash
amber
-
On
On
amber
amber
Slow flash
0.5s On and 0.5s Off
On initial power up all three LEDs (Y1, Y2 and G1) will switch On for approximately 1 second duration.
"
Ensure a shorting link is fitted to the programming header P1 located on the PSU. The link must be fitted
such that it shorts pins 1 and 2. This enables the EEPROM hardware write protect.
14
www.acornfiresecurity.com
FS3 3.15A(T)
Mains fuse
N
P1
P1
P3
43V
P7
FS6
BATT
Bat1 fuse
FS1 - 3.15A
G1
-
fast flash
green
-
slow flash
green
fast flash
green
fast flash
green
fast flash
green
-
fast flash
green
-
-
On
green
www.acornfiresecurity.com
N
PE
L
P2
L
PSU
See table below for LED illumination
information.
Y1
Y2
G1
amber
amber
green
24V supply fuse
FS4 - 1A
Description
Normal condition (no faults in the system)
Mains out of limit
24VDC failure only
Battery 1 failure only
Battery 1 and 24VDC failure
43VDC failure only
No power to PSU
Earth fault only

Advertisement

Table of Contents
loading

Table of Contents