The unit RWF Rotary Screw Compressor Units. data plate containing unit model, serial number and Frick sales order number is mounted on the side of the compres- For information about the functions of the Quantum control sor base.
1200 a mass is required to effectively dampen these relatively high frequency vibrations. Frick recommends consulting a licensed architect to deter- Firmly anchoring the compressor package to a suitable foun- mine the proper foundation requirements for any large en- dation by proper application of grout and elimination of pip- gine or turbine drive.
HOLDING CHARGE AND STORAGE Each RWF compressor unit is pressure and leak tested at COMPRESSOR/MOTOR COUPLING the Frick factory and then thoroughly evacuated and charged INSTALLATION with dry nitrogen to ensure the integrity of the unit during shipping and short term storage prior to installation.
Should additional heating capacity be required because of low ambient temperature, contact Current thermosyphon systems are using two-pass oil cool- Frick. The heaters are energized only when the unit is not in ers and flow rates based on 3:1 overfeed. operation.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM INSTALLATION Page 7 INSTALLATION - The plate and shell type thermosyphon 2. The liquid level in the refrigerant source must be 6 to 8 oil cooler with oil-side piping and a thermostatically con- feet minimum above the center of the oil cooler.
The water supply must be sufficient to meet the required flow. Frick recommends a closed-loop system for the waterside of the oil cooler. Careful attention to water treatment is es- sential to ensure adequate life of the cooler if cooling tower water is used.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM INSTALLATION Page 9 The recommended economizer systems are shown below. ECONOMIZER - HIGH STAGE (OPTIONAL) Notice that in all systems there should be a strainer (STR) and a check valve (VCK) between the economizer vessel The economizer option provides an increase in system ca- and the economizer port on the compressor.
Page 10 INSTALLATION noid on the PRR unit and the liquid feed solenoid on the DX chased separately from Frick . Starter packages should con- vessel off of a common signal to avoid liquid overfeed on sist of: the DX economizer system.
OPERATION and START-UP INSTRUCTIONS when facing the compressor drive shaft. (See Figure 12) The compres- The Frick RWF Rotary Screw Compressor Unit is an inte- sor should never be operated in reverse rotation as bear- grated system consisting of seven major subsystems: ing damage will result.
DO NOT ATTEMPT TO SERVICE THE COMPRESSOR OIL SEPARATION SYSTEM COLD START VALVE. PLEASE CON- TACT THE FRICK SERVICE The RWF is an oil flooded screw compressor. Most of the oil DEPARTMENT. discharged by the compressor separates from the gas flow in the oil charge reservoir.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 14 OPERATION COMPRESSOR HYDRAULIC SYSTEM SEE HYDRAULIC SCHEMATIC The compressor hydraulic system moves the movable slide FOR FUNCTIONAL valve (MSV) to load and unload the compressor. It also VIEW OF VALVE moves the movable slide stop (MSS) to increase or de- OPERATION crease the compressor’s volume ratio (Vi).
(PDCV) to prevent migration of high pres- sure gas during shutdown. A Frick-installed timer limits the 4. Monitor the oil temperature of the compressor. If the oil high pressure gas to only thirty seconds duration, since in- temperature rises above 170 °...
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 16 OPERATION SUCTION CHECK VALVE BYPASS LOW AMBIENT OPERATION The RWF unit is equipped with a low-pressure-drop suc- It is recommended that oil separators be insulated as a tion check valve bolted directly to the compressor housing. minimum requirement to preserve the heat generated by Units that have an 8"...
Initial start-up must be performed under the supervision run at the proper speed and discharge pressure. Exceed- of a FRICK authorized start-up representative to pre- ing design conditions creates a potential hazard. vent voiding the compressor warranty. Prior to the 3.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 18 MAINTENANCE GENERAL INFORMATION This section provides instructions for normal maintenance, a recommended maintenance program, troubleshooting and 1. IF UNIT IS RUNNING, PRESS [STOP] KEY. correction guides, and typical P and I diagrams. For typical 2.
6. Isolate the low pressure transducer, PE-4, to prevent Use of oils other than Frick Oil in damage during pressurization and leak test. Frick compressors must be ap- proved in writing by Frick engineer- 7.
5. Install new coalescer filter element(s). the oil-charging valve located on top of the separator. Using a pressure-type oil pump and recommended Frick oil, open Seat element in center of locating the charging valve and fill the separator until the oil level is tabs on separator bulkhead.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 21 oil will fill up in the separator faster than it shows in the the locknut counterclockwise and remove locknut. See Fig- sight glass. Refer to the table in the OIL CHARGE section ure 18 or 19.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 22 MAINTENANCE Clean all parts thoroughly and examine for wear or dam- 3. Start seal seat in seal housing bore. If force is neces- age. Check lip seals, ball bearings, bushing, and idler pin sary, protect seal face with a clean cardboard disc and gen- and replace if necessary.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 23 13. Pack lubrication chamber between inner ball bearing INSTALLATION OF CARBON GRAPHITE and double-row ball bearing in the thrust-bearing assem- BUSHINGS bly approximately one-half full of multipurpose grease, NLGI #2. The thrust-bearing assembly will take the remaining When installing carbon graphite bushings, extreme care space.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 24 MAINTENANCE Pressure Gauge - Discharge Port e. Relief valve set too low or stuck open. f. Pump worn out. 1. High reading would indicate: g. Tighten end clearance. a. High viscosity and small and/or long discharge line. h.
1. Only use Frick refrigeration oil or high quality refrigera- tion oils approved by Frick for your application. 2. Use vibration readings taken from the new unit at start-up as the base line reference.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 26 MAINTENANCE OPERATING LOG The use of an operating log as included in this manual (see Table of Contents) permits thorough analysis of the operation of a refrigeration system by those responsible for its maintenance and servicing. Continual recording of gauge pressures, tempera- tures, and other pertinent information, enables the observer and serviceman to be constantly familiar with the operation of the system and to recognize immediately any deviations from normal operating conditions.
COLD START VALVE. PLEASE CON- rary. When system conditions return to normal the units’ liq- TACT THE FRICK SERVICE DE- uid injection will overfeed and oil temperature will drop. In PARTMENT. solving the wrong problem a new problem was created.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 28 MAINTENANCE 6. Measure the voltage of PE-1 on connector P4 (termi- PRESSURE TRANSDUCER CONVERSION DATA nals WHT and BLK) on the SBC. 200 psi 500 psi Sensor Range - PSI Range - PSIG* 7.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 29 SV POSITION POTENTIOMETER REPLACEMENT AND ADJUSTMENT FLEXIBLE COUPLING The Slide Valve Position potentiometer is located on the end of the compressor unloader cylinder (applies to mod- POTENTIOMETER els 100 - 270), see Figure 23. 1.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 30 MAINTENANCE VOLUMIZER ® TRANSMITTER OIL LEVEL TRANSMITTER REPLACEMENT - SLIDE STOP REPLACEMENT ® The VOLUMIZER Transmitter is located on the right side of The Oil Level Transmitter is located on the front of the sepa- the compressor (facing shaft) at the inlet end (see Figure 25).
Unloader piston stuck. Contact Frick Factor or Frick service for assistance. Slipper seals worn out or damaged. Contact Frick Factor or Frick service for assistance. NOTE: Troubleshooting the compressor is limited to identifying the probable cause. If a mechanical problem is suspected contact the Service Department, Frick .
EITHER DIRECTION Solenoid service valves may be closed. Open. Manually actuate solenoid. If slide stop will not move mechanical problems are indicated. Consult Frick factor or Frick service. TROUBLESHOOTING THE LIQUID INJECTION OIL COOLING SYSTEM SYMPTOM PROBABLE CAUSES and CORRECTIONS HIGH OIL TEMPERATURE Insufficient liquid supply.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 33 TROUBLESHOOTING THE DEMAND PUMP SYSTEM SYMPTOM PROBABLE CAUSES and CORRECTIONS PUMP WILL NOT PRODUCE Check pump rotation. ENOUGH OIL PRESSURE TO START COMPRESSOR Check that service valves are open. Filter cartridges may be blocked. Check PSID across filters. Strainer may be blocked.
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 34 MAINTENANCE THERMAL EXPANSION VALVES In situations where system load conditions increase or de- crease over extended periods of time and the liquid injec- tion thermal expansion valve is not adequate for the new conditions, an improvement in valve performance may be achieved by increasing or decreasing discharge tube size.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 35 If the hole in the valve plate is to the left and the slot in the JORDAN valve disc is on the top this valve is set for Direct Acting (see TEMPERATURE REGULATOR VALVE figure 34).
130°F for ammonia and 140°F 11. Reattach the drive coupling. for R-22. Check with Frick service for recommended oil tem- peratures for other refrigerants. 12. The shaft alignment must be checked and tolerances verified with the Frick service dept.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 37 P & I DIAGRAM...
Page 38
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 38 MAINTENANCE P & I DIAGRAM - OPTIONAL DUAL OIL FILTERS, DEMAND OIL PUMP, THERMAL CONTROL VALVE SEPARATOR TO COMPRESSOR PALL TAHH OPTIONAL CV-2 DEMAND STR-2 OIL PUMP PM-1 CV-1 PDAH OF-1 OPTIONAL THERMAL REFRIGERANT...
Page 39
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 39 P & I DIAGRAM, LIQUID INJECTION – SINGLE PORT P & I DIAGRAM, LIQUID INJECTION – DUAL PORT...
Page 40
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 40 MAINTENANCE P & I DIAGRAM, LIQUID INJECTION – BOOSTER...
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 44 PROPER INSTALLATION OF ELECTRONIC EQUIPMENT PROPER INSTALLATION OF ELECTRONIC EQUIPMENT IN AN INDUSTRIAL ENVIRONMENT to provide a “clean” separate source voltage in order to In today’s refrigeration plants, electronic controls have found prevent EMI, from other equipment in the plant, from inter- their way into almost every aspect of refrigeration control.
Page 45
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM PROPER INSTALLATION OF ELECTRONIC EQUIPMENT Page 45 Never run any wires through an electronic control panel GROUNDING that do not relate to the function of the panel. Electronic control panels should never be used as a junction box. Grounding is the most important factor for successful op- These wires may be carrying large transients that will inter- eration and is also the most overlooked.
Page 46
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 46 PROPER INSTALLATION OF ELECTRONIC EQUIPMENT Never add relays, starters, timers, transformers, etc. in- PLANT SUPPLY side an electronic control panel without first contacting TRANSFORMER the manufacturer. Contact arcing and EMI emitted from 3-PHASE these devices can interfere with the electronics.
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 47 OPERATING LOG SHEET...
Page 48
The following items MUST be checked and completed by the installer prior to the arrival of the Frick Field Service Supervisor. Details on the checklist can be found in this manual. Certain items on this checklist will be reverified by the Frick Field Service Supervisor prior to the actual start-up. Mechanical Checks...
Page 49
H.P. _________ RPM ________ Serial # ________________________ Service Factor ______ Voltage ______ Hz __________ FLA ________ Design ______ Code ____ Starter Size ____ Special Options DX Economizer Frick Supplied Starter PC Control System Other Prestart Checks Position of all valves...
Page 50
S70-600 IOM RWF ROTARY SCREW COMPRESSOR UNITS Page 50 MAINTENANCE Adjustable Safety Setpoints High Discharge Pressure Stop Load _____ Force Unload ____ Alarm ______ Delay _____ Shutdown ____ Delay ____ High Discharge Temp. Stop Load _____ Force Unload ____ Alarm ______ Delay _____ Shutdown ____ Delay ____ Motor Amps ____ Volts _____ Service Factor _______ Horsepower _______ CT Factor ______ Recycle Delay ______...
Page 51
RWF ROTARY SCREW COMPRESSOR UNITS S70-600 IOM MAINTENANCE Page 51 VIBRATION DATA SHEET Date: _________________________________________ Sales Order Number: ____________________________ End User: _____________________________________ Installing Contractor: ____________________________ Address: ______________________________________ Service Technician: ______________________________ Final Hot Alignment Equipment ID (As in Microlog): _____________________ Compressor Serial Number: ______________________ Unit Serial Number: _____________________________ National Board Number: _________________________ Running Hours: ________________________________...
Need help?
Do you have a question about the RWF Series and is the answer not in the manual?
Questions and answers