60 Hz - Danfoss MLZ Selection & Application Manuallines

Refrigertion scroll compressors, 50-60 hz, r404a, r507, r134a, r22
Hide thumbs Also See for MLZ:
Table of Contents

Advertisement

A
PPLICATION GUIDELINES

60 Hz

SST = 20 °, SDT = 105 °F
RGT = 65 °F, SC = 0 °F
Models
Capacity
(Btu/h)
MLZ015
MLZ019
22 600
MLZ021
24 100
MLZ026
29 900
MLZ030
35 200
MLZ038
42 200
MLZ045
51 100
MLZ048
56 000
MLZ058
66 600
MLZ066
75 900
MLZ076
86 600
MLZ015
MLZ019
13 600
MLZ021
14 500
MLZ026
17 800
MLZ030
21 500
MLZ038
25 200
MLZ045
31 000
MLZ048
32 800
MLZ058
39 100
MLZ066
44 900
MLZ076
50 400
MLZ/MLM015
MLZ/MLM019
21 300
MLZ/MLM021
23 100
MLZ/MLM026
28 900
MLZ/MLM030
33 600
MLZ/MLM038
39 900
MLZ/MLM045
48 700
MLZ/MLM048
53 300
MLZ/MLM058
62 100
MLZ/MLM066
71 500
MLZ/MLM076
83 600
EER = Energy Efficiency Ratio
All performance data are for motor voltage code 4, 460 V / 3 ph / 60 Hz
* R507 performance data are nearly identical to R404A performance data
Capacity data at other conditions are available in the datasheets at: www.danfoss.com/odsg
T
ECHNICAL SPECIFICATIONS
SST = 25 °F, SDT = 105 °F
RGT = 65 °F, SC = 0 °F
Cold room
Ice machine
EER
Capacity
(Btu/h/W)
(Btu/h)
9.68
24 900
9.72
26 600
9.58
33 000
9.89
38 900
9.84
46 500
10.01
56 400
9.96
61 800
9.83
73 900
9.71
83 800
9.76
95 600
9.45
15 400
9.74
16 400
9.96
20 200
9.81
24 300
9.75
28 500
10.10
35 000
10.02
37 000
9.84
43 900
9.89
50 400
9.68
56 600
9.31
23 700
10.33
25 500
10.75
31 700
10.44
37 500
10.52
44 300
10.85
54 200
10.79
59 200
10.46
69 100
10.59
79 500
10.70
92 500
FRCC.PC.016.A1.22
SST = 32 °F, SDT = 105 °F
RGT = 65 °F, SC = 0 °F
Air drier
EER
Capacity
EER
(Btu/h/W)
(Btu/h)
(Btu/h/W)
10.71
28 500
12.29
10.76
30 400
12.33
10.58
37 800
12.12
10.88
44 400
12.41
10.82
53 100
12.33
11.05
64 500
12.62
10.96
70 600
12.51
10.80
84 900
12.26
10.61
95 900
11.96
10.68
109 400
12.05
10.59
18 100
12.32
10.91
19 300
12.71
11.14
23 800
12.94
11.01
28 700
12.84
10.94
33 700
12.73
11.32
41 200
13.20
11.20
43 500
12.99
10.90
51 400
12.49
10.94
59 000
12.53
10.72
66 200
12.29
10.37
27 400
11.93
11.63
29 400
13.35
11.76
36 200
13.25
11.54
43 300
13.13
11.52
51 000
13.06
11.96
62 500
13.61
11.92
68 300
13.60
11.58
80 000
13.29
11.68
91 700
13.34
11.83
106 200
13.46
SST = 25 °F, SDT = 110 °F
SST = 20 °F, SDT = 120 °F
RGT = 65 °F, SC = 0 °F
RGT = 65 °F, SC = 0 °F
Milk tank
ARI MT conditions
Capacity
EER
Capacity
(Btu/h)
(Btu/hr/W)
(Btu/h)
23 800
9.60
19 500
25 400
9.68
20 800
31 600
9.51
25 800
37 100
9.81
30 300
44 500
9.74
36 500
53 900
9.92
44 100
59 000
9.87
48 200
69 900
9.70
55 600
80 000
9.63
65 500
91 000
9.65
73 900
14 900
9.73
12 300
15 900
10.03
13 100
19 600
10.23
16 100
23 600
10.12
19 500
27 700
10.04
22 900
33 800
10.33
27 600
35 800
10.23
29 300
42 500
9.98
35 200
48 900
10.02
40 400
54 900
9.82
45 500
23 100
9.57
19 500
24 800
10.72
21 000
31 000
10.75
26 600
36 400
10.62
30 800
43 000
10.59
36 200
52 700
10.96
44 100
57 500
10.92
48 300
67 000
10.63
55 900
77 400
10.78
65 600
89 900
10.87
76 300
EER
(Btu/h/W)
6.93
6.99
6.88
7.13
7.12
7.17
7.19
6.94
7.17
7.09
7.31
7.54
7.69
7.59
7.50
7.59
7.56
7.51
7.57
7.38
7.28
8.08
8.12
8.10
8.10
8.26
8.21
7.95
8.28
8.23
9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MLZ and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents