Temperature Set Points; Calibration And Setting - Trane mP30 Installation Operation & Maintenance

Control for precision air conditioners
Table of Contents

Advertisement

UG30 CONTROL
To change set-points, you have to input the "USER" password to access the "SetP" menu in programming mode.
SEtP
S
ETTING
Temperature (summer) set-point. Used for setting the cooling set-point.
r1
Cooling differential.
r2
r3
Heating differential.
r4
Temperature neutral zone.
When the temperature measured by sensor B1 is within the neutral
temperature zone, all actuators are OFF, except in the following cases:
• Minimum ON time or the switch-off delay between the two compressors has
not elapsed yet;
• the compressors (or the valve) are operating following a dehumidification
request.
Delivery temperature lower limit.
rn
When the temperature read by delivery sensor B4 drops by 3°C below the set
limit (default = 15°C), the cold actuators (compressors or refrigerated water
valve) are switched off. The actuators are automatically restored when
temperature rises back to rn value.
SEtP
S
ETTING
r5
Humidity set-point
Humidification differential.
r6
r7
Dehumidification differential.
r8
Humidity neutral zone. When the temperature measured by sensor B3 is
within the neutral temperature zone, the 0-10V output, which activates the
humidifier, equals 0 and dehumidification is not active.
By using parameters
between the value measured by the sensor and the effective value measured by a precision instrument.
Prob
S
ENSORS
B1 sensor calibration. Room temperature.
6
B2 sensor calibration. External air temperature.
7
B3 sensor calibration. Room relative humidity.
8
B4 sensor calibration. Delivery temperature.
9
mP30-UG30 - Rev. 1.5 - Date: 18-03-2004
TEMPERATURE SET-POINTS
HUMIDITY SET-POINT
CALIBRATION AND SETTINGS
6,
7,
8,
9 the measurement of the sensors can be corrected if a difference is noted
EN
INSTRUCTION MANUAL
Minimum
Maximum Measurement
0
50
0.1
11.0
0.1
11.0
0.1
20.0
-20
30
Minimum
Maximum Measurement
20
90
1
20
1
20
0
20
Minimum
Maximum Measurement
-6.0
6.0
-6.0
6.0
-10
10
-6.0
6.0
Default
unit
°C
23
°C
1.5
°C
1.5
°C
0.2
°C
15
Default
unit
%R.H.
50
%R.H.
5
%R.H.
5
%R.H.
10
Default
unit
°C
0
°C
0
%R.H.
0
°C
0
33 (44)