SERVICE (cont.)
COMPRESSOR (DANFOSS) (ULTRA-1B) (cont.)
Removal and Replacement:
Compressor Start Relay: Refer to FIG. 30
1. Remove the terminal cover (4)
2. Disconnect the wires from the compressor start relay.
3. Pull relay (1) off of the compressor pins and discard.
4. Push new relay onto the compressor pins.
5. Refer to Fig. 30 and reconnect the wires.
6. Reinstall terminal cover (4).
FIG. 30 RELAY TERMINALS
Compressor Run Capacitor: Refer to FIG. 31
1. Remove terminal cover (4).
2. Disconnect the run capacitor leads.
3. Disconnect the run capacitor from the mounting bracket
located at the front of the dispenser chassis.
4. Remove run capacitor and discard.
5. Snap new run capacitor on the mounting bracket located
at the front of the dispenser chassis.
6. Refer to Fig. 31 and reconnect the wires.
FIG. 31 COMPRESSOR CAPACITOR TERMINALS
GRN
WHI
WHI/ORN to
Overload
Protector
BLK to Compressor
Relay
BLK to Compressor
Relay
38
Compressor Assy:
NOTE: Before removal of any refrigeration component the
refrigerant in the system must be reclaimed by a licensed
refrigeration repair person.
NOTE: When replacing the compressor it is recommended
that the dryer also be replaced.
1. Disconnect the tubes from the condenser and the ac-
cumulator.
2. Disconnect the compressor wiring harness from the
dispenser main wiring harness.
3. Remove the four .25-20 keps nuts and washers securing
the compressor to the chassis. Set nuts and washers
aside for reassembly.
4. Disconnect and remove the transformer.
5. From the right side of the dispenser lift the compressor
assembly over the four studs in the chassis and remove
compressor.
6. Install new compressor over the four studs in the dis-
penser chassis with the fill valve to the right side of the
dispenser.
7. Secure compressor to the dispenser chassis using four
.25-20 keps nuts and washers.
8. Reconnect tubes from the condenser and the accumula-
tor to the compressor.
9. Reinstall transformer.
10. Evacuate the system.
11. Recharge the 100V system with 6 oz. of Type 404A
refrigerant.
Design Pressures: High 330 - Low 60
NOTE: The charging of the system must be done by a li-
censed refrigeration repair person.
NOTE: Refer to Wiring Diagrams when reconnecting wires
to Compressor, Thermal Overload Protector, Start Relay,
and Run Capacitor.
41084 021710