■ Included accessories
Please confirm that the following accessory parts are included in the box.
1. Sensor case (top case, bottom case): x 1
2. Cross-slot pan-head screws M4x30: x 2
3. Wood screws 4.1x16: x 2
sensor cable (10 m (11 yards)): x 1
4. CO
2
5. LED cable (10 m (11 yards)): x 1
6. LED display explanation nameplate: x 1
7. Safety caution for installation: x 1
■ Specifications
Rated power supply voltage: 12 VDC (Supplied from the Lossnay)
Power consumption: 2 W or less.
Accessary wire length : 10 m (11 yards) [Maximum length is 20 m (22 yards) with field supply extension]
Usage environment: 0 to 40 ˚C (32 to 104 ˚F), 80 % RH or less. (No Cigarette Smoke or Sulfur and with no dew condensation)
Detection range: 300 to 2000 ppm
Measurement accuracy: ± (70 + 5% of measurement value) ppm
Weight: 1.1 kg
LOW (Green LED) : CO
concentration is below the threshold (1500 ppm at factory setting)
2
MID (Orange LED) : CO
concentration exceeds the threshold
2
HIGH (Red LED) : CO
concentration exceeds the threshold for a long time (20 minutes at factory setting).
2
* 1: In the range of 0 ˚C (32 ˚F) or less, CO
* 2: Measures the CO
concentration around the location where the CO
2
on the usage environment, installation conditions, etc. but this is not a malfunction.

3. Installation Method

3.1 Determine the installation location for the sensor case
Ensure that you adhere to the following points.
(1) Ensure clear space around the case as shown in the figure on the right, regardless of whether it is
installed using a switch box or on a wall.
(2) Source the following items locally.
- Putty
<Extra items required if installing using a switch box>
- Single-gang switch box
- Thin steel conduit
- Lock nut and bushing
Note:
- Direct sunlight sometimes cause the sensor case to discolor. Please be careful when
deciding the install position.
- Determine the sensor installation location only after checking with local laws and
regulations.
- Ensure that no objects are placed in the clear space around the sensor case to detect the
correct CO
concentrations.
2
- Ensure a flat surface is selected for the installation surface.
1
*
*
1
2
*
Sensor may not detect the correct CO
2
■ Outline drawings
70(2 3/4)
2
*
Concentration.
2
sensor is installed. In addition, the measurement accuracy may vary depending
2
2
Cable access hole
Minimum required space
around the CO
sensor
2
30 (1 3/16)
30 (1 3/16)
120 (4 23/32)
16
5/8
16
5/8
(
)
(
)
6
1/4
(
)
1.5(1/16)
or less
54
2 1/8
(
)
26(1 1/32)
Unit: mm (inch)
30 (1 3/16)
Unit: mm (inch)
8
(5/16)
20
13/16
(
)
10
3/8
(
)
44
1 3/4
(
)
Unit: mm (inch)