6.3 Auto fan speed setting without Lossnay or M-NET centralized remote controller
If not connecting remote controllers or M-NET centralized controllers to the Lossnay unit, set the "Auto fan speed setting without Lossnay or M-NET
centralized remote controller" dip switch to ON.
6.4 CO
sensor setting - maximum side and minimum side
2
The upper and lower limit of CO
The Lossnay unit controls its fan speed according to the set upper and the lower limit. Refer to the example on below.
Configure the settings from the remote controller CO
Instructions for the remote controller.
* Upper limit available setting range: 600 (lower limit + 300) to 2000 ppm (increments of 50 ppm)
* Lower limit available setting range: 300 to (upper limit - 300) ppm (increments of 50 ppm)
* This automatically controls the amount of airflow with the set CO
depending on the usage environment and product installation conditions, the value may exceed upper limit depending on the usage environment .
* If not using a remote controller, automatic airflow control will be carried out at the factory default setting.
* Factory default setting: Upper limit 1000 ppm, lower limit 450 ppm
<Example>
Auto fan speed with the following limits:
upper limit: 1000 ppm
CO
2
lower limit: 450 ppm
CO
2
(Factory setting)
6.5 CO
sensor correction
2
The CO
sensor recognizes the lowest CO
2
concentrations), and carries out calibration. The standard value for calibration is 400 ppm, however if this product is used in locations in which the
concentration is normally higher than the standard value (such as near a major highway), or in an interior environment with higher-than-
outside CO
2
concentrations, then there may be a significant discrepancy between the actual CO
normal CO
2
Therefore, configure the concentration correction function for CO
For how to configure the setting, refer to "CO
concentration display setting
6.6 CO
2
When using a remote controller, the CO
concentration display, refer to the remote controller Installation Manual, and set "Display details setting > Sensor value" to "Yes."
- To set the CO
2
- When displaying the CO
concentration, the supply air temperature cannot be displayed at the same time.
2
concentration display value may differ from the actual CO
- The CO
2
device.
- For approximately 15 minutes after turning the power on, or when changing 6.2 CO
During warm-up operation, the remote controller CO
- For approximately 15 minutes after starting operation, The CO
the room.
concentration display range is 400 to 2000 ppm. If the concentration exceeds 2000 ppm, "2000 ppm" will be displayed, and if less than 400
- The CO
2
ppm, "LO ppm" will be displayed. Additionally, the concentration is displayed in increments of 50 ppm from 400 to 1000 ppm, and increments of 100
ppm from 1000 to 2000 ppm.
6.7 PZ-70CSW-E LED setting
Wall mount type CO
sensor PZ-70CSW-E has LED which indicate the concentration level.
2
[LED operation overview]
The LED will light in accordance with the operations shown below. Settings thresholds and lighting times can be changed in the remote controller
function settings.
When the CO
exceeds the set threshold
value
(1) LED usage setting during non operation
It is possible to select lit or unlit during Lossnay unit is not operating.
The factory default setting is to turn on/turn off the LED display in accordance with Lossnay unit operation/shutdown.
For how to configure the setting, refer to "LED usage setting for PZ-70CSW-E during non operation" in the Installation Instructions for the Lossnay
unit.
(2) Threshold concentration
concentration at which the LED changes from "LOW (green)" to "MID (orange)" can be set within the range of 1000 to 2000 ppm.
The threshold CO
2
(increments of 100 ppm)
The factory default setting is 1500 ppm.
For how to configure the setting, refer to "Threshold concentration for PZ-70CSW-E LED" in the Installation Instructions for the Lossnay unit.
concentration are selectable.
2
control screen function settings. For how to configure the setting, refer to the Installation
2
(Fan output)
100%
95%
90%
85%
80%
75%
70%
65%
60%
55%
50%
45%
40%
35%
30%
25%
concentration over the previous week as the standard value (corresponding to normal outside CO
2
sensor correction" in the Installation Instructions for the Lossnay unit.
2
concentration can be displayed on the applicable Lossnay remote controller screen.
2
concentration display will show "---ppm."
2
concentration
2
When below the set threshold value
concentration as standard, however given that CO
2
450
1000
sensor output.
2
concentration within the room. This product cannot be used as a measurement
2
sensor setting, the CO
2
concentration display value may greatly differ from the actual CO
2
When the CO
concentration
2
remains at the set threshold
value for a set period of time
6
concentration detection will differ
2
* Fan output is switched in 16 steps for each CO
concentration equally divided between 450 ppm (CO
lower limit) and 1000 ppm (CO
(ppm)
concentrations and the detected concentrations.
2
sensor will be in warm-up operation.
2
2
2
upper limit).
2
2
concentration within
2