Download Print this page
Daikin DMVT P1400 Series Installation & Operating Instructions Manual

Daikin DMVT P1400 Series Installation & Operating Instructions Manual

Advertisement

Quick Links

DMVT***P1400**
AIR HANDLERS INSTALLATION &
OPERATING INSTRUCTIONS
1 Important Safety Instructions .................................... 3
2 Shipping Inspection ................................................... 3
2.1 Parts ....................................................................... 3
2.2 Handling ................................................................. 3
2.3 Shipping Material Removal..................................... 3
2.3.1 Blower Support Bracket Removal ....................... 3
3 Codes & Regulations ................................................. 3
4 Replacement Parts ..................................................... 3
5 Pre-Installation Considerations ............................... 3
5.1 Preparation ............................................................. 3
5.2 System Matches ..................................................... 3
5.3 Interconnecting Tubing ........................................... 3
5.4 Clearances ............................................................. 3
5.5 Horizontal Applications ........................................... 4
6 Installation Location ................................................... 4
6.1 Upflow and Downflow Installation (Figure 3 and 4) 4
6.2 Horizontal Left Installation (Figure 5)...................... 5
6.3 Horizontal Right Installation (Figure 6) ................... 5
6.4 Humid Environment Installations ............................ 5
6.4.1 All Installations – Humid Environments ............... 5
6.4.1.2 Downflow Installations – Humid Environments 5
6.4.1.3 Horizontal Installations – Humid Environments 5
7 Refrigerant Lines ........................................................ 6
7.1 Tubing Size ............................................................. 6
7.2 Tubing Preparation ................................................. 6
7.3 Tubing Connections ................................................ 7
7.4 Thermal Expansion Valve System Adjustment ....... 9
8 Condensate Drain Lines ........................................... 10
9 Ductwork .................................................................... 11
9.1 Return Ductwork .................................................... 11
10 Return Air Filters ..................................................... 11
11 Electric Heat ............................................................. 11
12 Electrical and Control Wiring ................................. 12
12.1 Building Electrical Service Inspection .................. 12
12.2 Wire Sizing .......................................................... 12
12.3 Maximum Overcurrent Protection (MOP) ............ 12
12.4 Electrical Connections – Supply Voltage ............. 13
DO NOT BYPASS SAFETY DEVICES.
RECOGNIZE SYMBOL THIS
AS A SAFETY PRECAUTION
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN
ARE SUBJECT TO CHANGE WITHOUT NOTICE
NOTICE: IF AN "Ec" error is encountered on startup, verify that the elec-
tric heater DIP switches have been set to the appropriate heater size. See
pages 14-17 for the heater kit airflow delivery and DIP switch settings.
Contents
WARNING
© 2022-2023
www.daikincomfort.com
19001 Kermier Rd., Waller, TX 77484
P/N: IOD-4040B Date: February 2023
Only personnel that have been trained to install, adjust,
service, maintenance or repair (hereinafter, "service")
the equipment specified this manual should service the
equipment.
This equipment is not intended for use by persons (including
children) with reduced physical, sensory or mental
capacities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning
use of the appliance by a person responsible for their
safety.
Children should be supervised to ensure that they do not
play with the equipment.
The manufacturer will not be responsible for any injury or
property damage arising from improper supervision, service
or service procedures. If you service this unit, you assume
responsibility for any injury or property damage which may
result. In addition, in jurisdictions that require one or more
licenses to service the equipment specified in this manual,
only licensed personnel should service the equipment.
Improper supervision, installation, adjustment, servicing,
maintenance or repair of the equipment specified in this
manual, or attempting to install, adjust, service or repair
the equipment specified in this manual without proper
supervision or training may result in product damage,
property damage, personal injury or death.
WARNING

Advertisement

loading
Need help?

Need help?

Do you have a question about the DMVT P1400 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Daikin DMVT P1400 Series

  • Page 1 DMVT***P1400** © 2022-2023 AIR HANDLERS INSTALLATION & www.daikincomfort.com OPERATING INSTRUCTIONS 19001 Kermier Rd., Waller, TX 77484 P/N: IOD-4040B Date: February 2023 Contents WARNING 1 Important Safety Instructions ........3 2 Shipping Inspection ........... 3 Only personnel that have been trained to install, adjust, 2.1 Parts ...............
  • Page 2 15 Troubleshooting ............18 15.1 Electrostatic Discharge (ESD) Precautions ..18 15.2 Diagnostic Chart ..........20 15.3 Fault Recall............20 16 Fully Communicating Daikin System ....20 16.1 Overview.............. 20 16.2 Airflow Consideration ........... 20 16.3 Control Wiring ............21 16.4 Fully Communicating Daikin System Advanced...
  • Page 3 HOMEOWNER SUPPORT 2 Shipping Inspection DAIKIN COMFORT TECHNOLOGIES Always transport the unit upright; laying the unit on its MANUFACTURING, L.P. side or top during transit may cause equipment damage.
  • Page 4 5.5 Horizontal Applications c. Reinstall the coil access panels and reinstall If installed above a finished living space, a secondary blower access panel removed in Step 1 as shown drain pan (as required by many building codes), must be in Figure 9. installed under the entire unit and its condensate drain line 6.
  • Page 5 NOTE: Do not use manifolds, copper lines, or the flowrator to pull the coil assembly out. Failure to do so may result in braze joint damage and leaks. 3. Removal of the center support is required on units with 21” wide cabinet. Remove and retain the two (2) screws that secure the center support to the cabinet.
  • Page 6 DFKE-02 DFKE-03 DMVT24B DMVT48C DMVT30B DMVT48D DMVT36B DMVT60D DMVT36C DMVT42C Table 3 6.4.1.3 Horizontal Installations – Humid Environments In addition to the High Humidity Kit (HHK), in applications where the air handler is installed in the horizontal position (Left or Right), and the return air environment sees humidity levels above 65% relative humidity, a Condensate Management Kit (CMK) must be used for field application.
  • Page 7 7 Refrigerant Lines WARNING WARNING A QUENCHING CLOTH IS STRONGLY RECOMMENDED TO THIS PRODUCT IS FACTORY-SHIPPED WITH R410A AND DRY PREVENT SCORCHING OR MARRING OF THE EQUIPMENT NITROGEN MIXTURE GAS UNDER PRESSURE. USE APPRO- FINISH WHEN BRAZING CLOSE TO THE PAINTED SURFACES. PRIATE SERVICE TOOLS AND FOLLOW THESE INSTRUC- USE BRAZING ALLOY OF 5% MINIMUM SILVER CONTENT.
  • Page 8 Upper Tie Plate Control Deck Blower Access Panel Downflow Coil Bracket Tubing Access Panel Panel Center Support Filter Bracket Filter Access Panel Knockout Internal Part Terminology External Part Terminology Figure 7 Figure 8 Coil Installation For Downflow Figure 9 Access Panel Configuration for Downflow or IMPORTANT NOTE: Ensure coil slides on the rails Horizontal Right along the groove provided on the drain pan side walls.
  • Page 9 7.4 Thermal Expansion Valve System Adjustment 3. Adjust Superheat by turning the TXV valve stem The following information for the indoor unit should be clockwise to increase and counterclockwise to verified before attempting to charge system or adjust TXV if decrease.
  • Page 10 NOTE: Water coming from secondary line means the SATURATED LIQUID PRESSURE coil primary drain is plugged and needs immediate TEMPERATURE CHART attention. SATURATED LIQUID LIQUID PRESSURE TEMPERATURE °F CAUTION PSIG R-410A IF SECONDARY DRAIN IS NOT INSTALLED, THE SECONDARY ACCESS MUST BE PLUGGED. Insulate drain lines located inside the building or above a finished living space to prevent sweating.
  • Page 11 11 Electric Heat IMPORTANT NOTE: The evaporator coil is fabricated with oils that may dissolve styrofoam and certain types Refer to the installation manual provided with the electric of plastics. Therefore, a removal pump or float switch heat kit for the correct installation procedure. All electric must not contain any of these materials.
  • Page 12 12.1 Building Electrical Service Inspection HEAT KIT NOMINAL kW This unit is designed for single-phase electrical supply 19/20 only. DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY. Measure the power supply to the unit. The supply 1000 voltage must be measured and be in agreement with the 1200 unit nameplate power requirements and within the range 1400...
  • Page 13 HEATER KIT (Kw) Model DMVT24BP14 DMVT30BP14 1050 DMVT36BP14 1050 DMVT36CP14 1020 1145 1345 DMVT42CP14 1020 1145 1345 DMVT48CP14 1045 1200 1420 1480 DMVT48DP14 1040 1170 1260 1300 1595 1595 DMVT60DP14 1135 1265 1375 1455 1815 1860 1925 *Airflows shown are to be considered the absolute minimum allowable for the Air handler and Heat kit combination. The minimum airflow does not represent the recommended airflow by the manufacturer.
  • Page 14 24 Volt Thermostat Wiring 12.4.1 Air Handler Only (Non-Heat Kit Models) IMPORTANT: Installation of Air Handler must follow any local codes/regulations. The manufacture recommends that when a heater kit is not installed, a field supplied WARNING disconnect switch or breaker should be installed in the electrical circuit that will allow power to be shut-off for HIGH VOLTAGE service or maintenance.
  • Page 15 4. Secure the dehumidistat ground wire (typically the Typical Single-Stage Cool, R C G Single-Stage Heat green lead) to the ground screw on the air handler. Heat Pump Thermostat NOTE: Ground wire may not be present on all Air Handler dehumidistats.
  • Page 16 This air handler is equipped with a multi-speed circulator 3. Knowing the air handler model, locate the high stage blower. This blower provides ease in adjusting blower cooling airflow charts in the Specification Sheet speeds. The Specification Sheet applicable to your model applicable to your model.
  • Page 17 Electric Heating Airflow Table. Configuring the dip switches and resetting power to the unit will clear the error code. Within the Daikin communicating thermostat user menu, will display 20 kW for OFF-OFF-ON dip switch selection and 21 kW for...
  • Page 18 7. If an electric heater kit has been installed, determine Outdoor Unit Tonnage the heater kilowatt (kW) rating. Using the Electric Heat Airflow table on page 16, set dip switches 9, Minimum 10, and 11 for the installed heater. The adjust setting Cooling/Heating CFM 1050 1225...
  • Page 19 Airflow Label Speed Selection Dip Switches Cooling/Heat Pump Airflow Table Continuous Profile Adjust Cool Selection Selection Selection Speed Switches Switches Switches Model Low Stage Cool High Stage Cool DMVT24BP14 DMVT30BP14 Profiles Pre-Run Short-Run OFF Delay 1050 ------ ------ 60 sec/100% DMVT36BP14 60 sec/100% ------...
  • Page 20 Communicating compatible air handler and air conditioner heat pump will calculate the system’s low stage cooling or heat pump with a Daikin Communicating thermostat. airflow demand. The heat pump will then send a fan Any other system configurations are considered invalid...
  • Page 21 If you are using a Daikin One+ Smart Thermostat, please terminal. Failure to do so may result in intermittent visit website at https://www.daikinone.com for instructions.
  • Page 22 17 Start-Up Procedure 16.5.1 Network Troubleshooting The Communicating system is a fully communicating WARNING system, and thus, constitutes a network. Occasionally the need to troubleshoot the network may arise. The integrated air handler control has some on-board tools that may be HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVIC- used to troubleshoot the network.
  • Page 23 19 Troubleshooting Chart Communications Troubleshooting Chart Indication Possible Causes Corrective Action(s) Notes & Cautions Status Normal condition None None None 1 Flash Communications Communications Depress Learn Button Depress once Failure Failure quickly for a power- Verify that bus BIAS and TERM up reset dipswitches are in the Depress and hold...
  • Page 24 19 Troubleshooting Chart Air Handler Advanced Features Menu DIAGNOSTICS Submenu Item Indication/User Modifiable Options Comments Fault 1 (FAULT #1) Most recent modular fault For display only Fault 2 (FAULT #2) Next most recent modular fault For display only Fault 3 (FAULT #3) Next most recent modular fault For display only Fault 4 (FAULT #4)
  • Page 25 19 Troubleshooting Chart...
  • Page 26 19 Troubleshooting Chart...
  • Page 27 19 Troubleshooting Chart...
  • Page 28 19 Troubleshooting Chart...
  • Page 29 20 Diagnostic Codes 7 SEGMENT LED (characters will DESCRIPTION OF CONDITION alternate) (no display) INTERNAL CONTROL FAULT / NO POWER HEATER KIT DIP SWITCHES NOT SET PROPERLY NO HTR KIT INSTALLED - SYSTEM CALLING FOR AUXILIARY HEAT BLOWER MOTOR OPERATING IN POWER, TEMP., OR SPEED LIMIT BLOWER MOTOR CURRENT TRIP OR LOST ROTOR OVER/UNDER VOLTAGE TRIP OR OVER TEMPERATURE TRIP INCOMPLETE PARAMETER SENT TO MOTOR...
  • Page 30 21 Wiring Diagram HIGH VOLTAGE! ISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT ULTIPLE POWER SOURCES MAY BE PRESENT AILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH 40 VA TRANSFORMER, SEE NOTE 1 230 VAC GRND GRND 208 VAC...
  • Page 31 21 Wiring Diagram 3 Phase Heat Kit Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 32 AIR HANDLER AIR HANDLER HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS Replace or Clean Filter An alternate cleaning method is to use one of the products listed in TP-109* to clean the coils. The cleaners listed are the only agents deemed safe and approved for use to IMPORTANT NOTE: Never operate unit without a filter clean round tube aluminum coils.
  • Page 33 22 Start-Up Checklist Air Handler / Coil Model Number Serial Number ELECTRICAL Line Voltage (Measure L1 and L2 Voltage) L1 - L2 Secondary Voltage (Measure Transformer Output Voltage) R - C Blower Amps Heat Strip 1 - Amps Heat Strip 2 - Amps BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure IN.
  • Page 34 THIS PAGE IS INTENTIONALLY LEFT BLANK...
  • Page 35 THIS PAGE IS INTENTIONALLY LEFT BLANK...
  • Page 36 CUSTOMER FEEDBACK Daikin Comfort Technologies is very interested in all product comments. Please fill out the feedback form on the following link: https://daikincomfort.com/contact-us You can also scan the QR code on the right to be directed to the feedback page.
Save PDF