6.7 Menu list

QM039 Issue 1
button functions are well known (see "7.1 Control and display
elements")
menu 1 – access protection
password active
PAon
to deactivate: set password
password inactive
PAof
to activate: set password
default setting for the password is "0005"; modification
of the password is described in special menu 4
menu 2 – set decimal point position
menus 3 and 4 – set zero point / end point
the device has been configured correctly before
delivery, so a later setting is only necessary, if a
differing displayed value is desired
(e. g. 0 ... 100 %)
menu 5 – set damping
this function allows getting a constant display value
although the measuring values may vary
considerably; the time constant for a simulated low-
pass filter can be set (0.3 up to 30 sec permissible)
menu 6 – exceeding message
set "on" or "off"
menus 7 – set switch-on point
set the values, for the activation of contact 1
menus 8 – set switch-off point
set the values, for the deactivation of contact 1
menus 9 – select hysteresis or compare mode
select hysteresis mode (HY 1) or compare mode
(CP 1) for contact 1
menus 10 – set switch-on delay
set the value of the switch-on delay after reaching
contact 1 (0 up to 100 sec permissible)
menus 11 – set switch-off delay
set the value of the delay after reaching switch-off
point 1 (0 up to 100 sec permissible)
menus 12 and 13 – maximum / minimum
pressure display
view high pressure (HIPr) or low pressure (LoPr)
during the measurement process
(the value will not remain stored if the power supply
is interrupted)
to delete: push both buttons again within one
second
menu 14 – measured value update (display)
set the length of the update cycles for the display
(0.0 up to 10 sec permissible)