XII. Disassembly of the 4900 Series POSRV (Cont.)
Part
Nomenclature
No.
M1
Base
M2
Base Plug
M3
Nozzle
M4
O-Ring (Nozzle)
M5
Retainer Nose
M6
O-Ring (Seat)
M7
O-Ring Retainer
M8
Lockscrew
M9
Guide Ring
M10
Disc
M11
O-Ring (Retainer Nut)
M12
O-Ring (Disc)
M13
Guide
M14
O-Ring (Coverplate)
M15
Base Stud
M16
Base Stud Nut
M17
Coverplate
M18
O-Ring (Guide)
M19
Sensing Element
M20 Retainer Nut
M21
Coverplate Plug
30 |
Baker Hughes
C. Cleaning
1. Clean parts to remove all rust, burrs, scale, organic matter, and
loose particles. Parts are to be free of any oil or grease except
for lubrication as specified in this instruction.
2. Cleaning agents used shall be such that effective cleaning
is assured without injuring the surface finishes or material
properties of the part.
3. Acceptable cleaning agents include demineralized water,
nonphosphate detergent, acetone, and isopropyl alcohol. Parts
must be blown dry or wiped dry after cleaning.
4. If you are using cleaning solvents, take precautions to protect
yourself from potential danger from breathing fumes, chemical
burns, or explosion. See the solvent's Material Safety Data
Sheet for safe handling recommendations and equipment.
5. Do not "sand blast" internal parts as it can reduce the
dimensions of the parts.