Baker Hughes product, or render it unsafe. It is also important to understand that these “safety messages” are not exhaustive. Baker Hughes can not possibly know, evaluate, and advise any customer of all of the conceivable ways in which tasks might be performed, or of the possible hazardous consequences of each way.
Unauthorized Removal of Seals: All new valves and valves repaired in the field Baker Hughes by Baker Hughes Field Service team are sealed to assure the customer of our guarantee against defective workmanship. Unauthorized removal and/or breakage of this seal will negate our warranty.
VIII. Introduction Design Features Baker Hughes's Consolidated 1900/P Series Steam Internals (conventional or bellows) safety valve is a precision machined device and operates on the force balance principle. Types 1900/P1 closed bonnet and P3 slotted bonnet valves have been designed for steam service in accordance with ASME Code Section I and VIII.
This manual provides plans for inspection and repair of Preventative maintenance should be practiced. At regular Consolidated 1900/P series steam internals safety valves. The intervals each valve should be removed, disassembled, requirements of this manual are considered minimum and do inspected, refurbished and tested to the customer’s...
All the upper internal parts can be removed as a unit by lifting out the spindle . These parts should be removed The Consolidated 1900/P series safety valve can be by lifting straight up. On bellows valves care should be disassembled by following the procedure outlined below: taken not to bend or distort the bellows or its flange.
Thermodisc™: because of the critical shape of the disc, flange to remove nozzle from base, or use a three-jaw chuck because of the critical shape of the disc, Baker Hughes does welded vertically to a stand bolted to the floor (see Figure 12).
If leakage is observed, the valve For hydro pressure exceeding 1.5 times the set pressure must be reworked. stamped on the name plate, Baker Hughes recommends that the valve be removed and a blind flange be installed to avoid E. Recommended Back Pressure internal damage to the valve.
To assist towards this objective, Baker Hughes recommends 5. Select parts and specify quantities. that the following guidelines be utilized to establish meaningful inventory levels.
“Hands On” experience with It is highly recommended that the professional talents of Consolidated valves. The seminar also includes valve a Baker Hughes Field Service Engineer be employed to terminology and nomenclature, component inspection, make final field adjustments during the initial setting of trouble shooting, setting and testing, with emphasis on all Consolidated Safety Valves.