Mitsubishi Electric VL-250CZPVU-R-E Installation Manual page 41

Lossnay heat recovery ventilator
Hide thumbs Also See for VL-250CZPVU-R-E:
Table of Contents

Advertisement

Function
Function name
No.
External output setting
81
3
Standard air speed
82
setting
Manual input priority
83
mode
CO
concentration
2
84
indication
In the following conditions, error code 3126 (malfunction on external devices) is displayed on the controller and the output of the function setting
No.81 [1] Malfunction monitor turns ON.
- When the built-in OA thermistor detects 15°C or higher within 15 minutes from the start of output of the supply air preheater/after-heater.
- When the built-in OA thermistor detects -10°C or lower 60 minutes after the start of output of the supply air preheater/after-heater.
Function setting value
[0]
[1]
[2]
[3]
Mal-
Supply
function
air shut-
monitor
ter
Enable (The following are the setting hours.)
Disen-
0.5
1.0
1.5
able
hour
hour
hours
hours
Hide Show
[4]
[5]
[6]
[7]
[8] [9]
− −
− −
− −
2.0
3.0
4.0
5.0
hours
hours
hours
− −
Eng-41
Factory
default
Function description
setting
Set the ON/OFF conditions of termi-
nal blocks TM3 8-10.
[1] Malfunction monitor:
Turns the output ON when a mal-
function occurs on the product. (This
is used to indicate malfunctions
aside from the controller.)
[2] Supply air shutter:
Set the setting so that the output
ON/OFF match with the open/closed
0
of the shutter installed on the OA
duct.
- Output ON (shutter: open) condi-
tions: 10 seconds before starting
the supply air operation
- Output OFF (shutter: closed)
conditions: The built-in thermistors
detect that the outdoor temperature
is -18°C or lower and 20 seconds
have elapsed after the supply air
fan stopped.
Set the base notch.
The setting can be changed in
0
6.4.2.7 Control mode. The priority is
given to the latest setting.
Set the setting so that the priority is
given to
,
for a certain time.
Use this when you want to give the
priority to the manual input (input
from the controller, MELCloud ap-
plication) rather than the external
input control.
Note
Just by ending the function,the
operation of the product may differ
0
from fan speed displayed on the
controller.
After changing the fan speed setting
of the controller once and about 5
sec. have passed, the operation of
the product will be the same as the
fan speed setting of the controller.
When set to
or
tion of the product returns to the fan
speed by external input after the
ending time elapses.
Set Show/Hide the CO
tion values connected to the Analog
input 1.
Set the settings of 6.4.2.4, and
6.4.5.2 also.
Lo is displayed when lower than 250
ppm and Hi is displayed when 2200
ppm or higher.
Note
0
If both function settings No. 38 and
84 are [1], only the function set-
ting No. 84: CO
concentration is
2
displayed on the «Main operation»
screen. (Since the same display
position is allocated, the priority is
given to the indication of function
setting No.84: CO
concentration.)
2
, the opera-
concentra-
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vl-250czpvu-l-eVl-350czpvu-r-eVl-350czpvu-l-e

Table of Contents