Installation Procedure - Mitsubishi Electric VL-250CZPVU-R-E Installation Manual

Lossnay heat recovery ventilator
Hide thumbs Also See for VL-250CZPVU-R-E:
Table of Contents

Advertisement

4. Installation Procedure

WARNING
Select a place which is strong enough to support the
product, and install the product securely.
Injury could result if parts fall.
CAUTION
Install the unit in the indoor side of the insulation layer/
airtight layer.
When installed on the outdoor side of the heat insulating
layer, the temperature of the heat-recovered air will drop and
condensation will form, which will cause the floor to get wet.
The products should be attached to a vertical surface.
The products may not be properly mounted and may cause
deformation of the product.
Transportation and installation of the product is carried
out by two or more people.
Cause of damage or injury of the product due to product fall.
Wear gloves when installing.
Failure to heed this warning may result in injury.
Note
- The unit is designed for wall mounting, only on a solid
wall. (Wall strength is needed more than 250 kg/m
- A gypsum block or stud/plasterboard wall will not
suffice.
4.1 Wall bracket
One pat of the wall bracket (supplied) should be offered up
to the wall, ensuring it's located horizontally. Make the fixing
points through the pre drilled holes in the bracket and install
with screws (normal diameter 4 mm), whilst ensuring the
interlock side is at the top.
Wall bracket
(Supplied)
Screw (normal diameter 4 mm)
(Field supply)
4.2 Mounting the Unit
CAUTION
Do not carry with a pipe guide.
Failure to heed this warning may result in damage to pipe
guide.
Do not place the product directly on the floor.
Failure to heed this warning may result in damage to the drain
pipe and the control box.
Wall bracket
Wall Mount Hook Center
2
.)
(unit)
4.3 Fixing the Unit
CAUTION
Install the product on the wall horizontally. (within ±1°)
Water leakage from the product may result in water damage
to the floor.
Note
- Use a washer(supplied), when there is a gap between
the attached surface and the hooks.
Eng-13
Control box
Drain pipe
Screw (normal diameter 4 mm)
(Field supply)