6.4.11 Maintenance interval
Set the maintenance interval of the filters.
After the fan operation time exceeds the product maintenance
interval, the maintenance sign (
operation» screen.
6.4.11.1 Accessing the «Maintenance interval» screen
Commissioning menu
Restriction
Error information
Error history
Run time
Maintenance interval
Main menu:
Cursor
Page
F1
F2
F3
6.4.11.2 Indication of Maintenance interval
Maintenance interval
Filter
Select:
Cursor
F1
F2
) will be displayed on the «Main
2/2
Auto bypass
Loading
F4
No /
Yes
4500
hour
Time
F3
F4
Press
and
to move the cursor.
Press
to go to the next screen.
The product data is loaded before the screen will appear.
[Loading] is displayed. (10-60 seconds)
Press
and
to move the cursor.
Press
and
to change the setting value.
Press
to go to the next screen.
Filter:
Select [Yes/No] to show the maintenance sign on the «Main
operation» screen.
The factory default setting: Yes
hour:
Change the maintenance interval.
The factory default setting: 4500 hours
Eng-38