Installation; Specifications - Breckwell BIG E Owner's Manual

Hide thumbs Also See for BIG E:
Table of Contents

Advertisement

SPECIFICATIONS

Width: 25 3/4"
Height: 32 5/8"
Depth: 23 7/8"
Weight: 275 lbs.
Flue Size: 3" or 4"
Hopper Capacity: Up to 140lbs.
(This can vary widely depending on
pellet size, length, and diameter.)
EPA status: exempt
Burn Time: 1lb to 5.5lbs. per hour
BTU range: 8,200 to 55,000
Approved installations: mobile home,
conventional
PREPARATION
Factory packaging must be removed,
and some minor assembly work is required
prior to installation. Access to the rear of
the stove is necessary.
NOTE: Normally, your dealer will perform
these functions.
CLEARANCES
This unit has been tested and listed
for installation in residential and mobile
homes.
FLOOR
PROTECTION:
installations,
minimum
32" deep. The stove must be placed
on a continuous (grouted joints) non-
combustible material such as ceramic
tile, cement board, brick, 3/8" millboard
or equivalent, or other approved or listed
material suited for floor protection.
THE
MATERIAL(S)
USED
OR COMBINE TO HAVE, A MINIMUM
INSULATIVE RATING OF 'R1.'
NOTE: ceramic tile, or any tile, requires a
continuous sheet beneath to prevent the
possibility of embers falling through to the
combustible if cracks or separation should
occur in the finished surface, this would
include floor protection for Built-in raised
hearths. Check local codes for approved
alternatives.
Clearances are measured from the sides,
back and face (door opening) or stove
body (refer to fig.2).
Clearances may only be reduced by
means
approved
by
authority having jurisdiction.
DO NOT USE MAKESHIFT MATERIALS OR
COMPROMISES IN THE INSTALLATION OF
THIS UNIT.
INSTALL VENT AT CLEARANCES SPECIFIED
BY THE VENT MANUFACTURER.
4

Installation

Freestanding
30"
wide
by
MUST
HAVE,
air distribution ductwork unless specifically approved for such
the
regulatory
BACK WALL
3"
WITH
VERTICAL
1"
EXHAUST
12"
MINIMUM SIDEWALL CLEARANCES
32"
6"
FLOOR PROTECTION
(MINIMUM 30" W X 32" D)
Caution: Do not connect to or use in conjunction with any
ADJACENT WALL
WITH
1"
HORIZONTAL
EXHAUST
FIGURE 1
30"
6"
FIGURE 2
installations.
3"
3"
1"
6"