Electrical installation

Important notes

Electrical installation
Important notes
DANGER!
Risk of injury and risk of burns from dangerous voltage
Power terminals may also carry voltage in the switched-off state or when the motor is stopped
and may cause life-threatening cardiac arrhythmia and serious burns.
▶ Disconnect the product from the mains.
▶ Check that the power terminals are deenergized before starting work.
When working on energized products, comply with the applicable national accident
prevention regulations.
The electrical installation must be carried out according to the appropriate regulations
(e.g. cable cross-sections, fuses, PE connection).
The manufacturer of the system or machine is responsible for adherence to the limits
required in connection with EMC legislation.
Operation on an external inverter
A max. pulse voltage amplitude of U
Here, the minimum pulse rise time must be t
If it cannot be ruled out that the permissible voltage peaks will be exceeded or that the
minimum pulse rise time will not be reached, the following measures must be initiated:
Reduction of the DC-bus voltage (threshold for brake chopper voltage)
Use of filters, chokes
Use of special motor cables

Preparation

The notes for the electrical connection can be found in the enclosed mounting
instructions.
EMC-compliant wiring
The EMC-compliant wiring is described in detail in the documentation of the
Lenze inverters.
20
= 1560 V at the motor terminals must not be exceeded.
pk
= 0.1 µs.
R