Installing The Control Panel - Dell PowerVault MD1000 Hardware Owner's Manual

Dell powervault md1000: owners manual
Hide thumbs Also See for PowerVault MD1000:
Table of Contents

Advertisement

Figure 3-8. Removing and Replacing the Control Panel
2
1
1
faceplate screws (16)
6 Using a Torx T10 driver, remove all 16 screws from the front faceplate of the enclosure as shown in
Figure 3-8.
7 Remove the front faceplate from the enclosure and place it on a flat, secure surface.
8 Slide the control panel assembly straight out from its connector on the backplane (see Figure 3-8).

Installing the Control Panel

1 Align the top and bottom tabs on the control panel with the insert slots on the edge of the chassis (see
Figure 3-8).
2 Slide the control panel fully into the slot, making sure that its connector engages into the matching
backplane connector (see Figure 3-8). Also, make sure the guide tab on the control panel is fully
inserted into the mounting slot on the backplane.
3 Replace the front faceplate and re-attach the 16 screws that hold it in place.
4 Re-install any drives you removed (see "Removing and Installing Drives").
5 Push the enclosure all the way back into the rack and tighten the thumbscrews securely.
6 Reconnect power cables to the enclosure and power it back on.
7 Power on the host server.