Troubleshooting - Berner Architectural Elite 8 Installation & Maintenance Instructions Manual

Table of Contents

Advertisement

SYMPTOMS
NO AIR
MINIMUM AIR
AIR IS NOT HITTING
FLOOR
UNEVEN AIR
EXCESSIVE AIR
MOVEMENT AT
DOORWAY
NO HEAT
MINIMAL HEAT
EXCESSIVE HEAT
X. TROUBLESHOOTING
CAUSE
• Power supply line open (no power)
• Fuse blown/circuit breaker tripped
• Motor overload tripped
• Failed switch
MOTOR RUNNING/FANS ARE NOT ROTATING
• Broken or flexible hub
• Shaft rotating inside fan
• Belt driven units/belt broken
ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN
• Selector switch is in off position
• Door limit switch not operating
• Air directional discharge vanes misadjusted
• Inadequate intake clearance
• Blower motor operates below speed
• Fan rubbing against housing
• Fan wheels clogged with dirt
• Air stream to weak
• Air stream hits obstruction
• Negative pressure
• Shaft rotating inside fan
• One motor not operating
• Nozzle not angled out far enough
• Unit too powerful
• Air movement too cold
• Pushing air outside building
SEE AIR IS NOT HITTING FLOOR SYMPTOMS
ELECTRICALLY HEATED MODELS
• Switch turned to "ON" position
• Thermostat not set properly
• Coils burned out due to lack of air
• Automatic reset thermal cutout failed in open position
• Manual reset thermal cutout tripped
• Low entering air temperature
• Thermostat in wrong location - thermostat too
close to discharge
• Improper voltage
• Thermostat not set properly
• Thermostat in wrong location
• Thermostat not set properly
• Insufficient air over coil
• Check power source, check method of control
position in ON
• Replace fuse(s)/reset breaker
• Internally protected motor - should reset automatically
after cool-down, if not replace motor.
• Replace switch
• Replace fan sleeve/reengage coupling
• Tighten set screws/tighten fan on shaft
• Replace belts
• Turn switch to "ON" position
• Repair or replace limit switch
• Adjust vanes to proper position, see instructions
• Move air curtain or remove obstruction
• Provide adequate space for air curtain
• Improve voltage
• Free fan from housing
• Clean and vacuum fan wheels
• Adjust nozzle to proper position, adjust motor speed;
see installation instructions
• Remove obstruction or reposition air curtain (move out
3
/
" for every 1" up from the door)
8
• Relieve negative pressure by providing make-up air
• Tighten set screws
• Repair or replace motor
• Adjust nozzle angle to outside
• Adjust motor speed
• Add auxiliary heat to overcome wind chill factor
• Adjust discharge angle back into building, adjust motor
speed
• Replace switch or check wiring
• Change thermostat setting
• Correct airflow problem; replace coils
• Replace automatic thermal cutout
• Reset manual thermal cutout
• Based on unit temperature rise, reduce speed
• Move thermostat away from air stream
• Supply proper voltage
• Change temperature setting
• Move thermostat closer to air stream
• change temperature setting
• Remove restriction on intake
- 14 -