Auxiliary Power Operation; Simultaneous Welding And Auxiliary Power Loads - Lincoln Electric Air Vantage 600X Operator's Manual

Diesel engine-driven welding power source
Table of Contents

Advertisement

AIR VANTAGE
600X
®

AUXILIARY POWER OPERATION

Start the engine and set the RUN / STOP / IDLE switch to the
desired operating mode. Full power is available regardless of the
welding control settings, if no welding current is being drawn.
The auxiliary power of the Air Vantage
15 amp VAC Australian 56SO315A receptacles with RCD
protection.
The auxiliary power capacity is 7,200 watts of 60 Hz, single
phase power. The auxiliary power capacity rating in watts is
equivalent to volt-amperes at unity power factor. The maximum
permissible current of the 240 VAC output is 15 A.
NOTE: The 240V receptacles are connected to different phases
and cannot be paralleled.
The auxiliary power receptacles should only be used with three
wire grounded type plugs or approved double insulated tools with
two wire plugs.
The current rating of any plug used with the system must be at
least equal to the current capacity of the associated receptacle.
TABLE B.5 AIR VANTAGE 600X SIMULTANEOUS WELDING AND POWER LOADS
Current
Voltage
Load
(Amps)
(Volts)
(Watts)
15
120
1800
15
240
3600
20
120
2400
20
240
4800
25
240
6000
30
240
7200
38
240
9000
50
240
12000
600X consists of two
®
WELD
AMPS
0
100
200
PLUS
250
300
400
Up To 600
TABLE B.6 AIR VANTAGE® 600X EXTENSION
CORD LENGTH RECOMMENDATIONS
Maximum Allowable Cord Length in ft. (m) for Conductor Size
14 AWG
12 AWG
30
(9)
40
(12)
60
(18)
75
(23)
30
(9)
60
(18)
Conductor size is based on maximum 2.0% voltage drop.
SIMULTANEOUS WELDING AND AUXILIARY POWER
LOADS
The auxiliary power capacity previously stated is maintained
without any welding load. If a welding load is present, the
available auxiliary power will decrease.
1 PHASE
WATTS
AMPS
7,500
15
7,500
15
7,500
15
7,500
15
7,500
15
5,600
14.4
0
0
10 AWG
8 AWG
75
(23)
125
(38)
150
(46)
225
(69)
50
(15)
88
(27)
100
(30)
175
(53)
90
(27)
150
(46)
75
(23)
120
(37)
100
(30)
B-18
OPERATION
6 AWG
4 AWG
175
(53)
300
(91)
350
(107)
600
(183)
138
(42)
225
(69)
275
(84)
450
(137)
225
(69)
250
(76)
175
(53)
300
(91)
150
(46)
250
(76)
125
(38)
200
(61)