6. Functions 2

6-1. Set Temperature Range Limit

The settable temperature range for the local remote controllers or the Web Browser for User can be limited.
By restricting the lower and upper limit of the set temperatures for cooling, heating, and auto modes, energy
consumption can be reduced.
Click [Functions 2] in the menu bar, and then click [Set Temperature Range Limit] to access the set temperature
range restrictions settings screen.
Note: Only the lower limit for the cooling mode and upper limit for the heating mode can be set for the ME remote
controller (PAR-F27MEA-E).
Note: The set temperature range restrictions settings may not be effective, depending on the unit model of the remote
controller and the indoor unit.
Note: A-control (Mr. Slim) units do not support the set temperature range restrictions settings.
Note: The set temperature range restrictions settings will be effective on the Web Browser for User, but not on the
Web Browser for System Maintenance Engineer. The temperature can be set to any temperature within the
unit's operable temperature range on the Web Browser for System Maintenance Engineer regardless of the set
temperature range restrictions settings.
Note: The set temperature range restrictions settings may not be accessible if logged in as a building manager.
Note: The set temperature limit range for the AUTO mode cannot be set for the groups that support the dual set point
function in the AUTO mode. The set temperature ranges for the normal cooling and heating modes will be used
for the ones for cooling and heating in the Auto (dual set point) mode.
Group No. and
group name
Refresh
Click to import the settings
from EB-50.
(1) Scroll up or down to display the group whose settings
are to be made. To make settings for all groups at once,
click [Batch Operations].
Then, click the [Set temperature range] area to display
the setting screen.
Set the temperature ranges for cooling, heating, and
auto modes.
Click [OK] to return to the previous screen.
Note: When the temperature unit is Fahrenheit,
temperatures are displayed in 2ºF increments.
Note: The temperature range for Dry mode will be the same
as the one for cooling mode.
(2) To copy the settings of a group to the settings for other groups, click [Copy] in the row of the group whose
settings are to be copied, then click [Paste] in the row of the group to which the copied settings are to be
pasted. The rectangular icons next to the selected buttons will appear in yellow-green.
42
Set temperature range
Batch Operations
Click to make settings for all
groups collectively.
Copy
Paste
Save Settings
Click to send the settings to
EB-50.

Advertisement

Table of Contents
loading

This manual is also suitable for: