The screen display under Action will vary, depending on the selected Output Unit Type.
(A) When [Group] is selected as the Output Unit Type
Click [Edit] under Action. The [Set up Actions]
screen will appear.
Set the interlocking actions to be taken when the
interlocking conditions are met.
Note: The current operation status will be maintained for the setting items that were not changed.
Note: The set temperature cannot be set unless the operation mode has been set.
Note: If the selected operation mode is not available on the interlocked output units, the Interlock Control will
not be performed.
Note: To prevent malfunctions of the air conditioning units, be sure to set the set temperature to a temperature
within the normal operating temperature range, although there may be rare cases in which it is possible
to set the set temperature to a temperature outside the normal operating temperature range (depending
on the model of the air conditioning units that are connected to a system).
Note: Signals for Swing and Auto of Air direction setting and Auto of Fan speed setting will not be output unless
these functions are available on the interlocked output units.
With respect to the air direction and fan speed, if the number of settable air directions and fan speeds
vary among the connected unit models, the signals that are rounded up to the settable range may be
output.
Note: When the interlocking conditions are met, it will take some time to issue the interlocking action
commands to the output units. This may delay the state change verification, which is usually performed
every three to five seconds.
(B) When [Free Output Points] is selected as the Output Unit Type
Select [ON] or [OFF] under Action to turn on or
off the output units.
55