5-2-2. Control details for outdoor units (All Peak Cut methods)
Follow the instructions below to make the Peak Cut control settings for each control level for given outdoor units.
Note: If the outdoor unit is a City Multi unit, the M-NET address will appear. If the outdoor unit is an A-control (Mr. Slim)
unit, the M-NET address and group name will appear.
Note: As for A-control outdoor units, only the inverter models can perform Peak Cut control. The Peak Cut control
settings for constant-speed models can not be made.
Control level
Batch Operations
Click to make settings for
all outdoor units at once.
(1) Scroll up or down to display the outdoor unit
whose settings are to be made. To make
settings for all outdoor units at once, check
the [Batch Operations] checkbox.
Then, set the maximum operating capacity for
each control level.
Outdoor units normally operate at the capacity
of 100%. The smaller the maximum operating
capacity, the more energy will be saved.
Note: Energy-saving effects cannot be expected
during low-load operation with the capacity
below the selected maximum capacity.
Note: For City Multi S series (PUMY) outdoor
units, leave the default setting [100%] as it
is not to activate the capacity-save control.
(2) For each control level, set the total time in which the Peak Cut control is performed during every
30 minutes. Setting the time to [30] or [15] minutes is preferable, for shorter control time is not likely to
bring much benefit.
If any time other than [30] minutes is selected, the outdoor units will operate in rotation so that they will not
perform the Peak Cut control at the same time.
(3) To copy the settings of an outdoor unit to the settings for other outdoor units, display the outdoor unit
whose settings are to be copied and click [Copy], then display the outdoor unit to which the copied settings
are to be pasted and click [Paste]. The rectangular icons next to the selected buttons will appear in yellow-
green.
Maximum Capacity
Select the upper limit of outdoor unit
operating capacity.
Capacity
e.g., Maximum capacity at 80%
80%
Operating
Capacity
No energy-saving effects
33
Copy
Paste
Control Time
Energy saved
Energy-saving effects
Time