Technical Data
Inputs
Outputs
Power supply
Power consumption
Set point range
Control accuracy
Proportional band
Dead band
Electrical connection
Operating temperature
Storage temperature
Relative Humidity
Degree of protection of housing
Weight
Interface
AM PM
. .
. .
MO TU WE TH FR SA SU
%RH
C
F
Dimensions
B
TFHB24F3XYZ1/100910
®
Communication Port
Features:
x
Attractive modern look with large LCD and backlight
x
Icons driven information and 1 line of text information
x
2 Pipes Analog, ON/OFF or Floating or
4 Pipes Analog, ON/OFF with local re-heat function
x
Auto fan and ON/OFF function enable or disable
x
External humidity sensor input and dehumidification sequence
(compensated by auto-activation of the reheat output)
x
Precise achieve temperature control with programmable PI function
x
Independent cooling & heating no occupancy set point
x
Lockable Set point / Control mode
x
Change over by contact or external temperature sensor
x
Celsius or Fahrenheit scale selectable
x
Anti-freeze protection
®
x
BACnet
MS/TP @ 9600, 19200, 38400, 76800bps
x
Selectable device Instance and MAC Address via technician menu
1 Fan analog or 3 Fan speed dry contracts 24Vac, 1A max 3A in-rush
2 Triacs output (cooling and/or heating) 24Vac, 0.3A max fused / triac
1 Triacs output (local reheat) 24Vac, 0.3A max fused / triac
Temperature: 10ºC to 40ºC [50ºF to 104ºF], Humidity: 10 to 65%RH
0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent)
0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/reheat independent)
Symbols on display
Cooling ON
A: Automatic
Heating ON
A: Automatic
Fan ON
A: Automatic
Humidity
E
D
-
A
C
Fan Coil Thermostat
Specification & Installation Instructions
TFHB24F3XYZ1
1 Digital input (24Vac or dry contact)
1 Analog input (humidification 0-10Vdc)
1 Analog input (change over 10Kohms or dry contact)
2 Analog outputs (cooling and/or heating 0-10Vdc)
1 Analog output (local reheat 0-10Vdc)
22 to 26Vac 50/60Hz
1 VA max
Temperature: ±0.4ºC [0.8ºF], Humidity: ±3.5%
2
0.8 mm
[18 AWG] minimum
0ºC to 50ºC [32ºF to 122ºF]
-30ºC to 50ºC [-22ºF to 122ºF]
5 to 95 % non condensing
IP 30 (EN 60529)
160 g. [0.36 lb]
Communication
Status
Menu set-up Lock
Programming mode
(Technician setting)
Dehumidification ON
Dimension
A
B
C
D
E
TFHB24F3XYZ1
Alarm status
Energy saving mode
Percentage of
%RH
humidity
ºC: Celsius scale
F
C
ºF: Fahrenheit scale
or
Imperial (in)
Metric (mm)
2.85
73
4.85
123
1.00
24
2.36
60
3.27
83
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the TFHB24F3XYZ1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Neptronic TFHB24F3XYZ1

  • Page 1 ® Fan Coil Thermostat with BACnet Communication Port Features: TFHB24F3XYZ1 Attractive modern look with large LCD and backlight Icons driven information and 1 line of text information 2 Pipes Analog, ON/OFF or Floating or 4 Pipes Analog, ON/OFF with local re-heat function...
  • Page 2: Mounting Instructions

    Specification & Installation Instructions TFHB24F3XYZ1 Mounting Instructions CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base. Remove the screw (captive) holding the base and the front cover of the thermostat. Lift the front cover of the thermostat to separate it from the base.
  • Page 3 Specification & Installation Instructions TFHB24F3XYZ1 Programming Mode When in this mode this symbol is displayed. Please press on button to advance to the next program function, press on button to return to preceding stage and press on button to change value. You can leave the programming mode at any time, changed values will be recorded.
  • Page 4 Specification & Installation Instructions TFHB24F3XYZ1 Step Display Description Values Set signal for 2 pipe system: Display shows “select 2 pipe signal” Cooling and heating symbols are also displayed. Select which signal output you want for your 2 pipe system. You can choose analog, on/off or floating output.
  • Page 5 Specification & Installation Instructions TFHB24F3XYZ1 Step Display Description Values Maximum voltage of the heating output: Display shows “max vdc analog output heating” and the value of the minimum voltage of the heating ramp. Range: 0.0 to 10.0 Volt Please select the desired value of the maximum voltage of the heating Increment: 0.1 Volt...
  • Page 6 Specification & Installation Instructions TFHB24F3XYZ1 Step Display Description Values Reheat dead band: Display shows “control dead band reheat” and the value of the reheat Dead band range : dead band, heating symbol is also displayed. 0.3 to 5.0ºC [0.6 to 10.0ºF] Please select the desired value of reheat dead band.
  • Page 7 Specification & Installation Instructions TFHB24F3XYZ1 Step Display Description Values Minimum voltage of the fan output: Display shows “min vdc analog output fan” and the value of the minimum voltage of the fan ramp. Range: 0.0 to 10.0 Volt Please select the desired value of the minimum voltage of the fan ramp.
  • Page 8 Specification & Installation Instructions TFHB24F3XYZ1 Step Display Description Values External humidity sensor offset Calibration: Display shows “extern humidty sensor offset” and relative humidity percentage read by external humidity sensor. Humidify symbol is also Range: 10 to 90%RH displayed. (max. offset ± 5%) Increment: 0.1%RH...
  • Page 9 Specification & Installation Instructions TFHB24F3XYZ1 Operation Mode Step Description Display At powering up, thermostat will light display and activate all LCD segments during 2 seconds. Illuminating the LCD. To illuminate the LCD, you just have to push onto any of the 4 buttons. LCD will light for 4 seconds.
  • Page 10 Specification & Installation Instructions TFHB24F3XYZ1 Notes:...
  • Page 11 Specification & Installation Instructions TFHB24F3XYZ1 Notes:...
  • Page 12 Specification & Installation Instructions TFHB24F3XYZ1 Notes: Recycling at end of life ® ® At end of life, please return the thermostat to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.