Neptronic TFCB24F3XYZ1 Specification And Installation Instructions

Neptronic TFCB24F3XYZ1 Specification And Installation Instructions

Fan coil thermostat with bacnet communication port
Hide thumbs Also See for TFCB24F3XYZ1:

Advertisement

Fan Coil Thermostat with BACnet
Features:

Technical Data

Inputs
Outputs
Power supply
Power consumption
Set point range
Control accuracy
Proportional band
Dead band
Electrical connection
Operating temperature
Storage temperature
Relative Humidity
Degree of protection of housing
Weight
Presentation
V
MAX
VDC
. .
. .
,
AM
PM
HR
V
MIN
SEC
%RH
C
F
Dimensions
B
TFCB24F3XYZ1.doc/100204
Communication Port
®
Attractive modern look with large LCD and backlight
Icons driven information and 1 line of text information
2 Pipes Analog, ON/OFF or Floating
4 Pipes Analog, ON/OFF with local re-heat function
Auto fan and ON/OFF function enable or disable
Precise achieve temperature control with programmable PI function
Independent cooling & heating no occupancy set point
Lockable Set point / Control mode
Selectable internal or external temperature sensor
Change over by contact or external temperature sensor
Celsius or Fahrenheit scale selectable
Anti-freeze protection
®
BACnet
MS/TP @ 9600,19200,38400,76800bps
Selectable device instance and MAC address via technician menu
1 Fan analog or 3 Fan speed dry contracts 24Vac, 1A max 3A in-rush
2 Triacs output (cooling and/or heating) 24Vac, 0.3A max fused / triac
1 Triacs output (local reheat) 24Vac, 0.3A max fused / triac
0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent)
0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/reheat independent)
Symbols on display
Cooling ON
33,66,100% output
A: Automatic
Heating ON
33,66,100% output
A: Automatic
Fan ON
rd
3
speed activated
A: Automatic
E
D
A
C
Fan Coil Thermostat
Specification & Installation Instructions
TFCB24F3XYZ1
1 Digital input (24Vac or dry contact)
1 Analog input (external temperature sensor 10KΩ)
1 Analog input (change over 10KΩ or dry contact)
2 Analog outputs (cooling and/or heating 0-10Vdc)
1 Analog output (local reheat 0-10Vdc )
22 to 26 Vac 50/60Hz
1 VA max
10ºC to 40ºC [50ºF to 104ºF]
Temperature: ±0.4ºC [0.8ºF]
2
0.8 mm
[18 AWG] minimum
0ºC to 50ºC [32ºF to 122ºF]
-30ºC to 50ºC [-22ºF to 122ºF]
5 to 95 % non condensing
IP 30 (EN 60529)
160 g. [0.36 lb]
Communication
Status
Menu set-up Lock
Programming mode
(Technician setting)
Dimension
A
B
C
D
E
TFCB24F3XYZ1
Alarm status
Energy saving mode
ºC: Celsius scale
F
C
ºF: Fahrenheit scale
or
Inches
Metric (mm)
2.85
73
4.85
123
1.00
24
2.36
60
3.27
83
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TFCB24F3XYZ1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Neptronic TFCB24F3XYZ1

  • Page 1: Technical Data

    Fan Coil Thermostat Specification & Installation Instructions Fan Coil Thermostat with BACnet Communication Port ® Features: TFCB24F3XYZ1 • Attractive modern look with large LCD and backlight • Icons driven information and 1 line of text information • 2 Pipes Analog, ON/OFF or Floating 4 Pipes Analog, ON/OFF with local re-heat function •...
  • Page 2: Mounting Instructions

    TFCB24F3XYZ1 Specification & Installation Instructions Mounting Instructions CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base. Remove the screw (captive) holding the base and the front cover of the thermostat. Lift the front cover of the thermostat to separate it from the base.
  • Page 3: Programming Mode

    TFCB24F3XYZ1 Specification & Installation Instructions Programming Mode When in this mode this symbol is displayed. Please press on button to advance to the next program function, press on button to return to preceding stage and press on button to change value. You can leave the programming mode at any time, changed values will be recorded.
  • Page 4 TFCB24F3XYZ1 Specification & Installation Instructions Step Display Description Values Set signal for 2 pipe system: “select 2 pipe signal” Display shows Cooling and heating symbols are also displayed. Select which signal output you want for your 2 pipe system. You can choose analog, on/off or floating output.
  • Page 5 TFCB24F3XYZ1 Specification & Installation Instructions Step Display Description Values Maximum voltage of the heating output: “max vdc analog output heating” Display shows and the value of the minimum voltage of the heating ramp. Range: 0.0 to 10.0 Volt Please select the desired value of the maximum voltage of the heating Increment: 0.1 Volt...
  • Page 6 TFCB24F3XYZ1 Specification & Installation Instructions Step Display Description Values Reheat dead band: “control dead band reheat” Display shows and the value of the reheat Dead band range: dead band, heating symbol is also displayed. 0.3 to 5.0ºC [0.6 to 10.0ºF] Please select the desired value of reheat dead band.
  • Page 7 TFCB24F3XYZ1 Specification & Installation Instructions Step Display Description Values Minimum voltage of the fan output: “min vdc analog output fan” Display shows and the value of the minimum voltage of the fan ramp. Range: 0.0 to 10.0 Volt Please select the desired value of the minimum voltage of the fan ramp.
  • Page 8 TFCB24F3XYZ1 Specification & Installation Instructions Step Display Description Values Heating set point during no occupancy: “no occ heating setpnt” Display shows and the value of the heating set point temperature during no occupancy period. Moon and heating Range: 10.0 to 40.0ºC [50 to 104ºF] symbols are also displayed.
  • Page 9 Note: These selections can vary according to the choice made on step #33 & #36. Recycling at end of life ® ® At end of life, please return the thermostat to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.

Table of Contents