Technical Data
Inputs
Outputs
Power supply 22 to 26Vac 50/60Hz
Power consumption 1VA
Set point range 10ºC to 40ºC [50ºF to 104ºF]
External sensor range -40ºC to 100ºC [-40ºF to 212ºF]
Control accuracy Temperature: ±0.4ºC [0.8ºF]
Proportional band 0.5ºC to 5ºC [1ºF to 10ºF] adjustable
Electrical connection 0.8 mm
Operating temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 to 95% non condensing
Degree of protection of housing IP 30 (EN 60529)
Weight 160 g. [0.36 lb]
Dimensions
A = 2.85" | 73mm
B = 4.85" | 123mm
C = 1.00" | 24mm
D = 2.36" | 60mm
E = 3.27" | 83mm
Interface
AM PM
. .
. .
MO TU WE TH FR SA SU
%RH
C
F
TRO24T4XYZ3-ESL-121002.doc
Features:
Attractive modern look with large LCD and backlight
Icon-driven information and 1 line of text information
Selectable analog and digital outputs
Precise temperature control with programmable PI function
Selectable Fahrenheit or Celsius scale
7-day schedule
2 or 4 daily independent time schedule and temperatures
AM/PM or 24-hour time display
Scheduling set point override
Multi level lockable access menu
Lockable set point
Selectable internal or external temperature sensor (10 KΩ)
Change over by contact or external temperature sensor
Pressure sensor input / air flow program
Selectable proportional control band and dead band
Anti-freeze protection
3 Universal analog inputs: 0-10Vdc, Thermistor (10k Type III), or digital input (dry contact)
Available for external temperature sensor, change over, night set back or pressure sensor
2 Analog outputs: 0-10Vdc or 2-10Vdc selectable (2mA max.)
4 TRIAC outputs: on/off, pulse 0 or 24Vac (250 mA max.),
or 2 Floating outputs
2
[18 AWG] minimum
B
E
D
ºF / º C
A
C
Symbols on display
Cooling ON
33,66,100% output
A: Automatic
Heating ON
33,66,100% output
A: Automatic
Alarm status
Day of the
MO TU WE TH FR SA SU
week
7-Day Programmable Room Thermostat
Specification & Installation Instructions
TRO24T4XYZ3
Menu set-up Lock
Programming mode
(Technician setting)
ºC: Celsius scale
C
F
ºF: Fahrenheit scale
or
Morning
AM PM
Afternoon
TRO24T4XYZ3
Morning
Day
Evening
Night
1
Need help?
Do you have a question about the TRO24T4XYZ3 and is the answer not in the manual?
Questions and answers