Technical Data

Inputs
Outputs
Power supply 22 to 26Vac 50/60Hz
Power consumption 1VA
Set point range 10ºC to 40ºC [50ºF to 104ºF]
External sensor range -40ºC to 100ºC [-40ºF to 212ºF]
Control accuracy Temperature: ±0.4ºC [0.8ºF]
Proportional band 0.5ºC to 5ºC [1ºF to 10ºF] adjustable
Electrical connection 0.8 mm
Operating temperature 0ºC to 50ºC [32ºF to 122ºF]
Storage temperature -30ºC to 50ºC [-22ºF to 122ºF]
Relative Humidity 5 to 95% non condensing
Degree of protection of housing IP 30 (EN 60529)
Weight 160 g. [0.36 lb]
Dimensions
A = 2.85" | 73mm
B = 4.85" | 123mm
C = 1.00" | 24mm
D = 2.36" | 60mm
E = 3.27" | 83mm
Interface
AM PM
. .
. .
MO TU WE TH FR SA SU
%RH
C
F
TRO24T4XYZ3-ESL-121002.doc
Features:
Attractive modern look with large LCD and backlight
Icon-driven information and 1 line of text information
Selectable analog and digital outputs
Precise temperature control with programmable PI function
Selectable Fahrenheit or Celsius scale
7-day schedule
2 or 4 daily independent time schedule and temperatures
AM/PM or 24-hour time display
Scheduling set point override
Multi level lockable access menu
Lockable set point
Selectable internal or external temperature sensor (10 KΩ)
Change over by contact or external temperature sensor
Pressure sensor input / air flow program
Selectable proportional control band and dead band
Anti-freeze protection
3 Universal analog inputs: 0-10Vdc, Thermistor (10k Type III), or digital input (dry contact)
Available for external temperature sensor, change over, night set back or pressure sensor
2 Analog outputs: 0-10Vdc or 2-10Vdc selectable (2mA max.)
4 TRIAC outputs: on/off, pulse 0 or 24Vac (250 mA max.),
or 2 Floating outputs
2
[18 AWG] minimum
B
E
D
ºF / º C
A
C
Symbols on display
Cooling ON
33,66,100% output
A: Automatic
Heating ON
33,66,100% output
A: Automatic
Alarm status
Day of the
MO TU WE TH FR SA SU
week
7-Day Programmable Room Thermostat
Specification & Installation Instructions
TRO24T4XYZ3
Menu set-up Lock
Programming mode
(Technician setting)
ºC: Celsius scale
C
F
ºF: Fahrenheit scale
or
Morning
AM PM
Afternoon
TRO24T4XYZ3
Morning
Day
Evening
Night
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the TRO24T4XYZ3 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Neptronic TRO24T4XYZ3

  • Page 1: Technical Data

    7-Day Programmable Room Thermostat Specification & Installation Instructions VAV Thermostat TRO24T4XYZ3 Features:  Attractive modern look with large LCD and backlight  Icon-driven information and 1 line of text information  Selectable analog and digital outputs  Precise temperature control with programmable PI function ...
  • Page 2: Mounting Instructions

    TRO24T4XYZ3 Specification & Installation Instructions Mounting Instructions CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base. Remove the screw (captive) holding the base and the front cover of the thermostat. Lift the front cover of the thermostat to separate it from the base.
  • Page 3: Programming Mode

    TRO24T4XYZ3 Specification & Installation Instructions Programming Mode When in this mode this symbol is displayed. Please press on button to advance to the next program function, press on button to return to preceding stage and press on button to change value. You can leave the programming mode at any time, ºF / º...
  • Page 4 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Set TO2 output signal: “select TO2 output signal” Display shows Select which signal output you want for TO2 output. You can choose on/off or pulse signal output. Default value: on-off Set TO2 signal ramp: “select TO2 ramp”...
  • Page 5 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Set motor direction: “select motor direct reverse” Display shows Select which direction you want for the motor. You can choose: Default value: direct (dir) Direct “clockwise” (0 to 90º) or Reverse “counter clockwise” (90 to 0º)
  • Page 6 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Set AO2 analog signal ramp: “select AO2 analog ramp” Display shows Select which ramp you want for analog signal on AO2. You can choose: Changeover ramp, Heating ramp 1, Heating ramp 2,...
  • Page 7 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Set AI1 input signal: “select AI1 input signal” Display shows Select which signal you want for AI1 input. You can choose:  OFF (input not used), External temperature function:  EtS (external temperature sensor 10KΩ), Changeover function: ...
  • Page 8 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Proportional band of changeover ramp: “control ramp Ch over” Display shows and the value of the changeover Proportional band range : ramp proportional band, cooling and heating symbols are also displayed.
  • Page 9 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Dead band in cooling ramp2: “control dead band 2 cooling” Display shows and the value of the Dead band range : cooling ramp2 dead band, cooling symbol is also displayed. Please select the desired value of cooling ramp2 dead band.
  • Page 10 TRO24T4XYZ3 Specification & Installation Instructions Air Flow Program Mode (Available when in Operation Mode; DS1.1 to OFF) Push on both buttons for 5 seconds to access the user air flow program mode. This menu is accessible only If ‘’PrSd’’ or ºF / º...
  • Page 11 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Maximum cooling airflow: “maximum cooling airflow” Display shows and the value of the maximum airflow in cooling. Range: minimum cooling airflow to Please select the desired value of the maximum airflow in cooling.
  • Page 12 TRO24T4XYZ3 Specification & Installation Instructions Scheduling Mode (Available when in Operation Mode; DS1.1 to OFF) Push the button for 5 seconds to access the user schedule menu. When in this mode, this symbol is displayed. Press on the ºF / º C...
  • Page 13 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Number of events/day: “Select 2 or 4 events per day” Display shows You can select 2 events or 4 events Default value: 2 day. Your selection will be applied for each day of the week.
  • Page 14 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Monday schedule programming Event 1: (If ‘’4’’ events was selected at step #4) “06:00:” Display shows and E1. MO and half sun symbols are also Range: 00:00 to Monday Event 2 displayed.
  • Page 15 TRO24T4XYZ3 Specification & Installation Instructions Step Display Description Values Monday schedule programming Event 3 heating set point: “adjust event 3 heating setpnt” Display shows and the value of the Set point range: heating set point temperature during this period. MO, half sun, moon and 10 to 40ºC [50 to 104ºF]...
  • Page 16 & #11 of scheduling mode. Recycling at end of life ® ® At end of life, please return the thermostat to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com.