Standard
IEC 61000-4-16
IEC 61000-4-8
CISPR 22
EN 55022
EMC Immunity Type Tests for IEEE 1613
Standard
Climatic Environmental Conditions
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
Mechanical Environmental Conditions
IEC 60068-2-6
Power Input
IEC 61000-4-11
EMC
IEC 61000-4-12
IEC 61000-4-4
IEC 61000-4-3
IEC 61000-4-2
Insulation
IEC 60255-5 (6.1.3)
IEC 60255-5 (6.1.4)
Military Standard Tests
Test
MIL-STD-810F
EMC and Environmental Type Tests
Method
IEC 61850-3 (5.7.3)
Low Frequency Conducted Susceptibility
IEC 61850-3 (5.7.3)
IEC 61850-3 (5.8)
IEC 61850-3 (5.8)
Method
IEEE 1613 (4.1.1)
IEEE 1613 (4.1.1)
High Temperature (Operational)
IEEE 1613 (4.1.2)
IEEE 1613 (4.1.2)
IEEE 1613 (4.1.3)
IEEE 1613 (10)
IEEE 1613 (10)
IEEE 1613 (5.1)
IEEE 1613 (7.3.1)
IEEE C37.90.1
IEEE 1613 (7.3.2)
IEEE C37.90.1
IEEE 1613 (8)
Radiated Susceptibility Immunity
IEEE C37.90.2
IEEE 1613 (9)
IEEE C37.90.3
IEEE 1613 (6.3
IEEE 1613 (6.2)
Description
Salt Fog
Description
Magnetic Immunity
Radiated Emission
Conducted Emission
Description
Low Temperature (Operational)
Low Temperature (Storage)
Low Temperature (Storage)
Humidity (Storage)
Shock (Drop)
Vibration
Voltage Variations
Oscillatory SWC
Fast Transient SWC
ESD
HV Impulse
Dielectric
Certification
Test Levels
30 V, 300 V Continues 3
V, 30 V 15 Hz to 150 kHz
100 A/m, 1000 A/m (1 sec)
30 MHz to 8 GHz
150 kHz to 30 MHz
Test Levels
-40 °C (-40 °F), 16 Hour Dwell
-65 °C (-149 °F), 16 Hour Dwell
-40 °C (-40 °F), 16 Hour Dwell
85 °C (185 °F), 16 Hour Dwell
95% at 55 °C (131 °F) for 96 Hours
1 m (3.3 ft), 1 Fall per Axis
2
2 g (32 ft/s
), 10-150 Hz per Axis
38.4 to 56 V
2.5 kV
4 kV
80 MHz to 1 GHz
20 V/m (unmodulated)
35 V/m (modulated)
8 kV Contact, 15 kV Air
5 kV
Test Levels
Method 509.4