Mounting and Commissioning
3.3 Commissioning
Test in Message Direction
For all information that is transmitted to the central station, test the options in the list which appears in SET-
POINT Status:
• Make sure that each checking process is carried out carefully without causing any danger (see above and
refer to DANGER!)
• Click on Send in the function to be tested and check whether the transmitted information reaches the central
station and shows the desired reaction. Data which are normally linked via binary inputs (first character ">")
are likewise indicated to the central power system with this procedure. The function of the binary inputs itself
is tested separately.
Exiting the Test Mode
To end the System Interface Test, click on Close. The device is briefly out of service while the start-up routine
is executed. The dialog box closes.
Test in Command Direction
The information transmitted in command direction must be indicated by the central station. Check whether the
reaction is correct.
3.3.4

Communication Module Configuration

Required Settings in DIGSI 4 and DIGSI Manager
In order that the device can access the new communication module, a change has to be made in the parameter
set within the DIGSI Manager.
In DIGSI 4 Manager, select the SIPROTEC device in your project and select the menu item "Edit" - "Object
properties..." to open the "Properties - SIPROTEC 4 Device" dialog box (see following Figure ). In the "Communi-
cation modules" tab, select the type of communication module or the protocol for "11. Port F" using the "L: ..."
button.
Figure 3-22
98
DIGSI 4: Protocol Selection (Example)
SIPROTEC, 6MU805, Manual
C53000-G1140-C380-5, Release date 06.2018