Neptronic HRO20LSS Specification And Installation Instructions

Neptronic HRO20LSS Specification And Installation Instructions

Humidity controller

Advertisement

Quick Links

Model
HRO20LSS
Description
The Humidity Controller is a combination controller and
humidistat. The Humidity Controller is an advanced application
to control relative humidity for general purpose applications.
They are specially designed to control humidifiers and
dehumidification equipment.
Features
Outputs & Inputs
• 4 analog outputs (0-10 Vdc or 2-10 Vdc)
• 2 dry contact outputs
• External humidity sensor input
• Window or external temperature sensor input
• Alarm status input
• Low signal selector input
Operation & Display
• Wall mounted controller
• Adjustable setpoint with auto reset from external sensor
• Multi level lockable access menu
• Lockable setpoint and control mode
• Backlit LCD with simple icon and text driven menus
• Selectable Celsius or Fahrenheit scale
• Humidification and dehumidification indicator
Technical Specifications
Description
Outputs
Inputs
Power supply
Power consumption
Setpoint range
Sensor precision
Proportional band
Electrical connection
Operating condition
Storage condition
Housing degree of protection
Weight
HRO20LSS-141202-ETL
- Actual humidity (0-100% RH), 0-10 Vdc/2-10 Vdc
- Humidity setpoint (0-100% RH), 0-10 Vdc/2-10 Vdc
- Humidification proportional control signal, 0-10 Vdc/2-10 Vdc
- Dehumidification proportional control signal, 0-10 Vdc/2-10 Vdc
- Humidification dry contracts 24 Vac, 1 A max, 3 A in-rush
- Dehumidification dry contracts 24 Vac, 1 A max, 3 A in-rush
- Low signal selector (LSS) - (0-10 Vdc/2-10 Vdc) or high limit external humidity sensor
(0-10 Vdc/2-10 Vdc)
- External setpoint from Neptronic humidifier, external humidity sensor (0-10 Vdc/2-10 Vdc), or
Low Signal Selector(LSS) - (0-10 Vdc/2-10 Vdc)
- 1 alarm status digital input (24 Vac or dry contact)
22 to 26 Vac 50/60 Hz or 28 to 32 Vdc
1 VA
10%-90% RH (in 1% increments)
± 3% or better at 40% RH and 23ºC [73ºF]
2%-10% for control signal
2
0.8 mm
[18 AWG] minimum
0ºC to 40ºC [32ºF to 104ºF], 0-95% RH
-10ºC to 50ºC [14ºF to 122ºF], 0-95% RH
IP 30 (EN 60529)
130 g. [0.3 lb]
Humidity Controller
Specification and Installation Instructions
HRO20LSS
HRO20LSS
Page | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HRO20LSS and is the answer not in the manual?

Questions and answers

Summary of Contents for Neptronic HRO20LSS

  • Page 1 - Low signal selector (LSS) - (0-10 Vdc/2-10 Vdc) or high limit external humidity sensor (0-10 Vdc/2-10 Vdc) Inputs - External setpoint from Neptronic humidifier, external humidity sensor (0-10 Vdc/2-10 Vdc), or Low Signal Selector(LSS) - (0-10 Vdc/2-10 Vdc) - 1 alarm status digital input (24 Vac or dry contact)
  • Page 2 E = 3.27” | 83mm Wiring We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment.
  • Page 3: Mounting Instructions

    This is useful for humidistats installed in areas where the humidity read is slightly different than the room’s actual humidity. For example, a humidistat placed right under the air diffuser. www.neptronic.com Page | 3...
  • Page 4: Humidity Settings

    The setpoint value is restricted by the minimum (Step 3 “adjust minimum user setpnt”) and maximum (Step 4 “adjust maximum user setpnt”) values. In other words, the setpoint should be within the minimum and maximum setpoint range. www.neptronic.com Page | 4...
  • Page 5: Analog Outputs (Ao1 To Ao4)

    If you selected dEHU at Step 6 “adjust control mode”, go to Step 17 “select AI1 input signal”. “min vdc analog ao4 output” Default: 0.0 Volt Range: 0.0, 2.0 Volt Select the desired value of the minimum voltage of AO4 output. The humidify symbol is also displayed. www.neptronic.com Page | 5...
  • Page 6: Analog Inputs (Ai1 And Ai2)

    External Humidity External Setpoint from Low Signal Selector Low Signal Selector Input not used Sensor 0-10 Vdc Sensor 2-10 Vdc Neptronic Humidifier 0-10 Vdc 2-10 Vdc “extern humidty sensor offset Ai1” Range: 10 to 90% RH Offset: Max. ± 5% Increment: 0.1% RH...
  • Page 7: Operation Mode

    The temperature reading is displayed for 2 seconds. If the sensor is disconnected or short circuited, then “- - -” is displayed. To toggle the temperature scale between ºC and ºF, press both keys for 3 seconds. www.neptronic.com Page | 7...
  • Page 8: Humidity Setpoint Adjustment Mode

    The Control Mode appears for 5 seconds. The following options are available: • Humidify only/OFF • Dehumidify only/OFF • Automatic Humidify and Dehumidify/OFF These options can vary according to the choice made in Step 6 “adjust control mode” of the Programming Mode. www.neptronic.com Page | 8...
  • Page 9: Wiring - Humidistat And Humidifiers

    L o w v o lta g e c o n tro l te rm in a l b lo c k te rm in a l b lo c k In te rlo ck * www.neptronic.com Page | 9...
  • Page 10: Sks Humidifier

    7 0 0 M A C O M C O M M A X . T B 1 T B 2 H R O 2 0 L S S h u m i d i s t a t www.neptronic.com Page | 10...
  • Page 11: Skr Humidifier

    A cce ss p a n e l C O M 2 4 V A C L S S / H L M O D H R O 2 0 L S S h u m i d i s t a t www.neptronic.com Page | 11...
  • Page 12 Specification and Installation Instructions Notes Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com. 400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com...

Table of Contents