Models
EVCB14NIT0S
(0 TRIACS / pressure independent)
EVCB14NIT2S
(2 TRIACS / pressure independent)
EVCB14NIT4S
(4 TRIACS / pressure independent)
EVCB14NIT4X
(4 TRIACS / independent / external motor)
EVCB14NDT4X
(4 TRIACS / dependent / external motor)
EVCB14NDT4S
(4 TRIACS / pressure dependent)
EVCB14NIT0SF
(0 TRIACS / independent / feedback)
EVCB14NIT4SF
(4 TRIACS / independent / feedback)
For use with either floating or modulating actuators
TRL54
(Thermostat 3x3)
Description
The EVCB Series is a combination controller and thermostat with
support for networked communications via the BACnet MS/TP or
Modbus protocol. The Networkable VAV Controller is designed for
simple and accurate control of any variable air volume box in a
number of zone control configurations. Its field configurable
algorithms enable versatile implementation of required control
sequences.
Typical Application
Features
Field configured VAV algorithms, inputs and outputs
Built-in actuator, 70 lb-in. (select models, not available on
EVCB14NIT4X and EVCB14NDT4X)
Control external actuators using analog (0-10Vdc, adjustable)
or floating signals with feedback (models EVCB14NIT4X and
EVCB14NDT4X)
On board differential pressure sensor (select models)
Simple air balancing and commissioning via thermostat
Automatically sets operation mode to pressure dependent or
independent based on the presence of air flow
Select direction on analog outputs
Configurable PI (Proportional-Integral) function
Independent, configurable proportional control band and dead
band per ramp
Selectable internal or external temperature sensor (10KΩ)
External CO2 sensor input with integrated logic
Changeover by contact or external temperature sensor
Internal and external temperature sensor calibration
Optional potentiometer feedback for increased precision of
actuator position
Freeze protection
Removable, raising clamp, non-strip terminals
Operational Features
Backlit LCD with simple icon and text driven menus
Select thermostat's default display
Network service port via on-board mini USB connector
Manual night set back or no occupancy override
Multi level lockable access menu and setpoint
Selectable Fahrenheit or Celsius scale
3-wire connection to controller and 4 push buttons
EVCB14N-TRL54-V505-191004-ESA
Networkable VAV Controller
Specification and Installation Instructions
EVCB Series / TRL54
Applications
Single duct, cooling only
Single duct cooling and/or heating
Up to 4 stage reheat and/or cool
Up to 4 On/Off heat and/or cool
Up to 4 time proportioned (TPM) heat or reheat
Up to 2 analog (0-10Vdc) reheat and/or cool
Up to 2 floating heat and/or cool
Pressure dependent or pressure independent
With or without auto changeover
Supply/exhaust (requires an additional EVC)
Network Communication
BACnet MS/TP or Modbus communication port
Select MAC address via DIP switch or via network
Automatic baud rate detection
BACnet MS/TP®
Automatic device instance configuration
Copy & broadcast configuration via thermostat menu
or via BACnet to other controllers
BACnet scheduler
Firmware upgradeable via BACnet
Support for COV (change of value)
Modbus
Modbus @ 9600, 19200, 38400 or 57600 bps
RTU Slave, 8 bits (configurable parity and stop bits)
Connects to any Modbus master
Page | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVCB Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Neptronic EVCB Series

  • Page 1 For use with either floating or modulating actuators TRL54 (Thermostat 3x3) Description The EVCB Series is a combination controller and thermostat with support for networked communications via the BACnet MS/TP or Modbus protocol. The Networkable VAV Controller is designed for EVCB Series / TRL54 simple and accurate control of any variable air volume box in a number of zone control configurations.
  • Page 2: Controller Specifications

    B = 3.00 in (78mm) C = 1.00 in (24mm) D = 2.36 in (60mm) The thermostat functions only with the EVCB Series controller. All the inputs/outputs are located on the EVCB Series Note except for the temperature sensor built-in the thermostat.
  • Page 3 D = 5.50" | 140mm A = 7.20” | 183mm EVC with a separate 180 in. lb. Actuator B = 1.23” | 31mm C = 2.93” | 74mm D = 4.02” | 102mm E = 1.78” | 45mm www.neptronic.com Page | 3...
  • Page 4: Mechanical Installation

    COMMON (-) (black) FEEDBACK (green) SUPPLY (+) (red) CONTROL (white) Signal cable from EVC controller (models EVCB14NIT4X and EVCB14NDT4X) Use to connect the external motor on EVCB14NIT4X and EVCB14NDT4X. Green: Feedback White: Control Red: 24Vac Black: Common www.neptronic.com Page | 4...
  • Page 5: Mounting Instructions

    DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance 153000 153001 153002 153003 153004 … … … … … … … … … … 153126 153127 * Slave addresses available by setting DS.8 to ON www.neptronic.com Page | 5...
  • Page 6 Specification and Installation Instructions Wiring We strongly recommend that all Neptronic products be wired to a separate grounded transformer and that transformer shall service only Neptronic products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. Room Module (TRL54)
  • Page 7 NSB, proportional bands, and deadbands, will be erased and reset to factory default values. (ITOS) (fan powered box ON) (fan powered box Auto) T MM (Outputs) (Temperature) Mt MM (Motor) SEt MM (Settings) (Ramps) NEt MM (Network) (Time & Date) (Buttons) www.neptronic.com Page | 7...
  • Page 8 (dI2 delay seconds) (Buttons) 1 (override heat 1) AV.64 (normally open) (0-3600 sec) 2 (override heat 2) C (normally closed) t (override all heat) L (normally cool) Go to “OuT" MM t (normally heat) † D (unoccupied damper) www.neptronic.com Page | 8...
  • Page 9 2 (heating ramp 2) L (pulsed) 2 (carbon dioxide) (setpnt airflow 0-10Vdc)§ (changeover ramp)§ (cool/heat 1)§ (analog 0-10Vdc)§ † (fan follows demand) Go to “t4C TO4 Close Percent” † (fan continuously on) Go to “to4 TO4 DIR-REV” www.neptronic.com Page | 9...
  • Page 10 (fan follows demand) † available with models: (fan continuously on) SEt MM (Settings) - EVCB14NIT4S - EVCB14NDT4S - EVCB14NIT4SF = Available on models EVCB14NIT4X and (Ramps) EVCB14NDT4X only NEt MM (Network) (Time & Date) (Buttons) www.neptronic.com Page | 10...
  • Page 11 -EVCB14NDT4S -EVCB14NDT2 (CO2 control mode) BV.101 Go to “NEt" MM (open) Go to “NEt" MM 4 (CO2 prop band) AV.190 4 (CO2 dead band) AV.191 (control) 100ppm 20ppm (50-250 ppm) (10-50 ppm) www.neptronic.com Page | 11...
  • Page 12 (Network) (AM/PM format) Go to “BtN" Local Date Local Date (Month) (1-12) (1-31) (Time & Date) = select / set value Go to “PrS" (Arrows key locked) (Bottom left key locked) (Upper left key locked) (Buttons) www.neptronic.com Page | 12...
  • Page 13: Operation Menus

    (Start address) (End address) to normal operation Go to AV.167 AV.165 (0-254: max=start + 63) AV.166 (cancel) (in progress) (done) (0-254) “ENd" (confirm) Refer to Copy Config Annnex for a complete list of messages and error codes. www.neptronic.com Page | 13...
  • Page 14: Reset To Factory Default Settings

    *** Pressing the button returns to the previous step without saving *** Note: Refer to EVCB-Airflow Balance Instructions on Neptronic website for further information on the airflow balancing function. Pressure Dependent: models EVCB14NDT4S, EVCB14NDT4X or other models if in pressure dependent mode...
  • Page 15 = select / set value Local Time Local Time Local Date Hours Minutes Year Set Time Display format (1-24 or 1-12 am/pm) (00-59) (15-99) (24-hour format) (AM/PM format) Month Go to “PrSs" (1-12) (1-31) Local Date Local Date www.neptronic.com Page | 15...
  • Page 16 Fan Auto = Fan powered box in automatic mode (follows demand) nSb.o = Night Set Back (normally open) Occ.o = Occupancy mode (normally open) = TRIAC output = Analog output = Analog input = Digital input www.neptronic.com Page | 16...
  • Page 17 Notes...
  • Page 20 Recycling at end of life: please return this product to your Neptronic local distributor for recycling. If you need to find the nearest Neptronic authorized distributor, please consult www.neptronic.com. 400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada www.neptronic.com Toll free in North America: 1-800-361-2308 Tel.: (514) 333-1433...