To Access Mode 1 Or 2; To Use Mode 1; To Use Mode 2 - Daikin VRV IV-S RXYSQ4T8VB Series Installation And Operation Manual

Hide thumbs Also See for VRV IV-S RXYSQ4T8VB Series:
Table of Contents

Advertisement

BS4
TEST: For test operation
BS5
RESET: For resetting the address when the wiring is
changed or when an additional indoor unit is installed
7‑LEDs display
The display gives feedback about the field settings, which are
defined as [Mode-Setting]=Value.
H1P
Shows the mode
H2P~H7P
Shows the settings and values, represented in binary code
H8P
NOT used for field settings, but used during initialisation
Example:
[
-
32
+
16
+
8
+
4
+
2
+
1]
H1P
H1P H2P H3P H4P H5P H6P H7P
(H1P OFF)
(H1P flashing)
(H1P ON)
0
+
0
+
8
+
0
+
0
+
0
(H2P~H7P = binary 8)
0
+
0
+
0
+
4
+
0
+
0
(H2P~H7P = binary 4)
16.1.4

To access mode 1 or 2

After the units are turned ON, the display goes to its default
situation. From there, you can access mode 1 and mode 2.
Initialisation: default situation
NOTICE
Be sure to turn ON the power 6 hours before operation in
order to have power running to the crankcase heater and
to protect the compressor.
Turn on the power supply of the outdoor unit and all indoor units.
When the communication between indoor units and outdoor unit is
established and normal, the display indication state will be as below
(default situation when shipped from factory).
a
Power ON
b
Default situation
c
LED indication when there is a malfunction
If the default situation is not displayed after 10~12 minutes, check
the malfunction code on the indoor unit user interface. Solve the
malfunction code accordingly. First, check the communication wiring.
Switching between modes
Use BS1 to switch between the default situation, mode  1 and
mode 2.
RXYSQ4~6T8V/YB(*)
VRV IV-S system air conditioner
4P482275-1B – 2020.10
Description
Default situation
Mode 1
Mode 2
Setting 8
(in mode 2)
Value 4
(in mode 2)
a
10~12 min
b
c
a
b
c
a
Default situation (H1P OFF)
b
Mode 1 (H1P flashing)
c
Mode 2 (H1P ON)
BS1
Press BS1.
BS1 [5 s]
Press BS1 for at least 5 s.
INFORMATION
If you get confused in the middle of the process, press BS1
to return to the default situation.
16.1.5

To use mode 1

In mode 1 (and in default situation) you can read out some
information.
Example: 7‑LEDs display – Default situation
You can read out the status of low noise operation as follows:
#
Action
1
Make sure the LEDs are
showing the default situation.
2
Check the status of LED
H6P.
Example: 7‑LEDs display – Mode 1
You can read out setting [1‑5] (=  the total number of connected
indoor units) as follows:
#
Action
1
Start from the default
situation.
2
Select mode 1.
3
Select setting 5.
("X×" depends on the setting
that you want to select.)
4
Display the value of setting 5.
(there are 8 indoor units
connected)
5
Quit mode 1.
16.1.6

To use mode 2

In mode 2 you can make field settings to configure the system.
Example: 7‑LEDs display – Mode 2
You can change the value of setting [2‑8] (=  T
during cooling operation) to 4 (= 8°C) as follows:
#
Action
1
Start from the default
situation.
16 Configuration
Button/display
(H1P OFF)
H6P OFF: Unit is currently
not operating under low noise
restrictions.
H6P ON: Unit is currently
operating under low noise
restrictions.
Button/display
BS1 [1×]
BS2 [X×]
(= binary 5)
BS3 [1×]
(= binary 8)
BS1 [1×]
target temperature
e
Button/display
Installation and operation manual
29