28 | Fan Motor Options

Constant Airflow Motors (ECM)

For installations where constant air delivery is
critical or where external static pressure drop can
vary greatly (such as with high MERV value filters)
the LV series is offered with a constant air flow
ECM motor option. This option provides ECM
motor efficiency combined with a constant air
delivery across a wide range of external static
pressures. These motors dynamically adjust their
power output to precisely match the desired air
flow on a pre-programmed fan curve. Additionally
these motors feature:
1. A low CFM ventilation feature that circulates
air at 70% of full load when fan only is called.
2. A passive dehumidification mode that reduces
air flow during a cooling call when
dehumidification is also required – this
reduces the sensible heat ratio of the cooling
coil and extends cooling run time to more
effectively dehumidify. (refer to the ECM
Interface Board section of this manual)
Table 7: Constant Airflow Motor Performance Table
Fan
Rated
Model
Speed
Airflow
A - Low
A -
LV-015
Normal
500
A - Hi
B - Low
B -
LV-018
Normal
650
B - Hi
C - Low
C -
LV-024
Normal
850
C - Hi
D - Low
D -
LV-030
Normal
950
D - Hi
A - Low
A -
LV-036
Normal
1200
A - Hi
A - Low
A -
LV-041
Normal
1200
A - Hi
8 733 905 683 (2013/04)
0.10
0.20
0.30
0.40
450
450
450
450
500
500
500
500
580
580
580
580
550
540
540
540
650
650
650
650
750
750
750
750
720
720
720
720
850
850
850
850
960
960
960
960
810
810
810
810
950
950
950
950
1090
1090
1090
1090
1020
1020
1020
1020
1200
1200
1200
1200
1380
1380
1380
1380
1020
1020
1020
1020
1200
1200
1200
1200
1380
1380
1380
1380
Subject to change without prior notice
3. 3 speed settings per model. Units are factory
set to "NORM" but can be field adjusted to "+"
to increase CFM by 15% or to "-" to reduce
CFM by 15%. (refer to the ECM Interface
Board section of this manual)
4. A "TEST" mode that operates the motor at a
70% torque setting. This setting can be used
to diagnose programming problems in the
motor itself. (refer to the ECM Interface Board
section of this manual)
5. A CFM indicator light that provides a blink for
each 100 CFM of air delivered (note that this
blink code is approximate and should not
replace test and balancing).
Refer to the constant air flow motor performance
tables for heat pump blower performance with the
constant air flow motor option.
0.50
0.60
0.70
0.80
450
450
450
440
500
500
500
480
580
580
580
570
540
540
540
530
650
650
640
630
750
750
740
730
720
720
720
700
850
850
850
850
960
960
960
960
810
810
810
810
950
950
950
950
1090
1090
1090
1090
1020
1020
1020
1020
1200
1200
1200
1200
1380
1380
1380
1380
1020
1020
1020
1020
1200
1200
1200
1200
1380
1380
1380
1380
LV Heat PumpSeries
0.90
1.00
1.10
1.20
440
430
-
-
470
460
-
-
560
550
-
-
520
500
-
-
610
590
-
-
710
690
-
-
650
560
-
-
800
700
-
-
880
790
-
-
810
810
-
-
950
950
-
-
1090
1090
-
-
1020
1020
-
-
1200
1200
-
-
1380
1380
-
-
1020
1020
-
-
1200
1200
-
-
1380
1380
-
-
LV Heat Pump Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents