46 | Waterside Pressure Drop Table
WATERSIDE PRESSURE DROP TABLE
Water Flow
Model
Rate (GPM)
1.5
LV007
2
2.5
2
LV009
2.5
3
2.5
LV012
3
3.5
3
LV015
4
5
4
LV018
5
6
4
LV024
6
8
5
LV030
7.5
9
6
LV036
9
12
7
LV041
10
13
7
LV042
10
13
8
LV048
12
15
10
LV060
15
18
11
LV070
16
18
All values based upon pure water at 70 deg F.
8 733 905 683 (2013/04)
Water Side Pressure Drop with
out Internal Valve (PSI)
0.7
1.1
1.7
1.7
2.5
3.5
2.6
3.6
4.8
3.9
6.5
9.8
2.7
4.0
5.6
2.8
5.8
9.7
3.0
6.2
8.6
2.6
5.4
9.1
3.6
6.9
11.1
3.6
6.9
11.1
1.4
2.8
4.2
2.3
4.8
6.7
2.9
5.7
7.0
Subject to change without prior notice
Water Side Pressure Drop with Internal
Valve (PSI)
1.0
1.7
2.5
2.2
3.3
4.6
3.4
4.7
6.2
5.0
8.3
12.5
4.5
6.7
9.3
3.3
6.8
11.4
3.7
7.7
10.7
3.6
7.5
12.6
5.0
9.5
15.2
5.0
9.4
15.1
2.1
4.4
6.6
3.5
7.2
10.0
4.2
8.3
10.3
LV Heat PumpSeries