Step 5 - Field Fabricate Ductwork; Step 6 - Rig And Place Unit - Bryant 581J Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit sizes 07, 08, 09 & 12 with puron (r--410a) refirgerant
Table of Contents

Advertisement

Fig. 6 - - Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
For vertical ducted applications, secure all ducts to roof curb
and building structure. Do not connect ductwork to unit.
Fabricate supply ductwork so that the cross sectional
dimensions are equal to or greater than the unit supply
duct opening dimensions for the first 18 in. (458 mm) of
duct length from the unit basepan.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
MAX WEIGHT
UNIT
LB
581J*07
1200
581J*08
1420
581J*09
1420
581J*12
1665
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the unit center of gravity. Use
wooden top to prevent rigging straps from damaging unit.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
B-C
A-C
0.5" (13)
1.0" (25)
1.0" (25)
C06110
KG
IN
545
88.0
645
88.0
645
88.0
757
88.0
Fig. 7 - - Rigging Details
A minimum clearance is not required around ductwork.
!
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in damage
to roofing materials.
Membrane roofs can be cut by sharp sheet metal
edges. Be careful when placing any sheet metal parts
on such roof.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a
reference. See Table 1 and Fig. 7 for additional information.
Lifting holes are provided in base rails as shown in Fig. 7.
Refer to rigging instructions on unit.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
Before setting the unit onto the curb, recheck gasketing on
curb.
DIMENSIONS
A
B
MM
IN
2235
44.0
2235
44.0
2235
44.0
2235
32.0
11
CAUTION
CAUTION
C
MM
IN
MM
1120
41.5
1055
1120
49.5
1255
1120
49.5
1255
815
49.5
1255
C06005