Step 5 - Field Fabricate Ductwork; Step 6 - - Rig And Place Unit - Bryant 551J Installation Instructions Manual

Single package rooftop cooling only sizes 04-06 with puron (r-410a) refirgerant
Table of Contents

Advertisement

Fig. 4 - - Unit Leveling Tolerances
Step 5 — Field Fabricate Ductwork
Cabinet return-air static pressure (a negative condition)
shall not exceed 0.35 in. wg (87 Pa) with economizer or
0.45 in. wg (112 Pa) without economizer.
j
For vertical ducted applications, secure all ducts to roof
curb and building structure on vertical ducted units. Do
not connect ductwork to unit.
Insulate and weatherproof all external ductwork, joints,
and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through unconditioned spaces must be
insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with
applicable fire codes.
UNIT
LB
551J*04A
700
551J*05A
830
551J*06A
865
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the
unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.
MAXIMUM ALLOWABLE
DIFFERENCE IN. (MM)
A-B
B-C
A-C
0.5" (13)
1.0" (25)
1.0" (25)
MAX WEIGHT
KG
IN
318
74.5
377
74.5
393
74.5
Fig. 5 - - Rigging Details
For units with accessory electric heaters: Horizontal
applications require a minimum clearance to combustible
surfaces of 1- - in (25 mm) from duct for first 12- - in (305 mm)
away from unit. Vertical applications do not require a
minimum clearance around ductwork.
Step 6 — Rig and Place Unit
Keep unit upright and do not drop. Spreader bars are not
required if top crating is left on unit. Rollers may be used
to move unit across a roof. Level by using unit frame as a
reference. See Table 1 and Fig. 5 for additional
information.
C06110
Lifting holes are provided in base rails as shown in Fig. 5.
Refer to rigging instructions on unit.
Before setting the unit onto the curb, recheck gasketing on
curb.
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in
equipment damage.
All panels must be in place when rigging. Unit is not
designed for handling by fork truck.
If using top crate as spreader bar, once unit is set,
carefully lower wooden crate off building roof top to
ground. Ensure that no people or obstructions are
below prior to lowering the crate.
DIMENSIONS
A
MM
IN
1890
36.5
1890
36.5
1890
36.0
8
CAUTION
B
C
MM
IN
925
33.5
925
41.5
915
41.5
C06005
MM
850
1055
1055