6.14

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the knob of the gas maximum pressure switch to the
minimum end of scale position
 Turn the air pressure switch knob to the maximum end of
scale position
 Turn off the burner and cut off the power
 Disconnect the minimum gas pressure switch connector
 Disconnect flame detection sensor electrical connections
Make sure that the mechanical locking systems
on the adjustment devices are fully tightened.
WARNING
20148180
Start-up, calibration and operation of the burner
The burner must stop
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to ignition
failure
36
GB
Tab. Q