4.7

Firing rates

The MAXIMUM OUTPUT is chosen from within the continuous
diagram area (Fig. 2).
The MINIMUM OUTPUT must not be lower than the minimum
limit of the diagram:
RLS 1000/M MX = 3750 kW
RLS 1200/M MX = 5500 kW
26
24
22
20
18
16
14
12
10
8
6
4
2
0
1000
4.8

Test boiler

The burner/boiler combination does not pose any problems if the
boiler is EC approved and its combustion chamber dimensions
are similar to those indicated in the diagram (Fig. 3).
If the burner must be combined with a boiler that has not been EC
approved and/or its combustion chamber dimensions are clearly
smaller than those indicated in the diagram, consult the
manufacturer.
The firing rates were obtained in special test boilers, according to
EN 676 standard.
20148180
Technical description of the burner
RLS 1000/M MX
1800
2600
3400
4200
5000
The firing rate value (Fig. 2) has been obtained
considering an ambient temperature of 20 °C, an
atmospheric pressure of 1013 mbar (approx. 0 m
a.s.l.), and with the combustion head adjusted as
WARNING
shown on pag. 19.
5800
6600
7400
8200
Thermal power - kW
In Fig. 3 you can see the diameter and length of the test
combustion chamber.
Example:
Output 7000 kW - diameter 120 cm - length 6 m
MODULATING RATIO
The modulating ratio, obtained in test boilers, according to
standard (EN 676 for gas, EN 267 for light oil), is of 4:1 for light
oil and 7:1 for gas.
10
GB
D11552
RLS 1200/M MX
9000
9800
10600
11400 12200
D2448
Fig. 2
Fig. 3