Measures - GE Multilin HID Instruction Manual

High impedance differential module
Table of Contents

Advertisement

4.5

MEASURES

Latching relay coil resistor (only for latching relay option) :
NOTE: An error of 20% will be admitted
Resistors Measure:
Check that the resistor value between terminals is:
• 2K with latching relay
• 1K without latching relay
NOTE: An error of 12% will be admitted
C12 – D8
C11 – D7
C10 – D6
Thyrites current measure:
GEK-113064
ACCEPTANCE TESTS
Latching relay
Terminals A1 – A3
option
1 (48 Vdc)
2 (125 Vdc)
3 (220 Vdc)
Thyrite Terminals
C12 – D4
C11 – D3
C10 – D2
HID High Impedance Differential Module
Terminals B10 – B12
340 Ohm
2K15
4K2
Applied voltage
290 Vac
2 - 10 mA
2 – 10 mA
2 - 10 mA
340 Ohm
2K15
4K2
4-3

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Multilin HID and is the answer not in the manual?

Questions and answers

ILIYA ILIEV
January 24, 2025

Wiring diagram for HID30 (w/o latching relays) is missing. Only for HID32 is available. Please provide it. Thank you!

1 comments:
Mr. Anderson
February 10, 2025

The wiring diagram for the GE Multilin HID30 without latching relays can be found in the external wiring diagram section of the manual. It is advised to check the corresponding external wiring diagram specific to the HID model being used.

This answer is automatically generated

This manual is also suitable for:

Multilin hid3210.320.704

Table of Contents