4.5
MEASURES
Latching relay coil resistor (only for latching relay option) :
NOTE: An error of 20% will be admitted
Resistors Measure:
Check that the resistor value between terminals is:
• 2K with latching relay
• 1K without latching relay
NOTE: An error of 12% will be admitted
C12 – D8
C11 – D7
C10 – D6
Thyrites current measure:
GEK-113064
ACCEPTANCE TESTS
Latching relay
Terminals A1 – A3
option
1 (48 Vdc)
2 (125 Vdc)
3 (220 Vdc)
Thyrite Terminals
C12 – D4
C11 – D3
C10 – D2
HID High Impedance Differential Module
Terminals B10 – B12
340 Ohm
2K15
4K2
Applied voltage
290 Vac
2 - 10 mA
2 – 10 mA
2 - 10 mA
340 Ohm
2K15
4K2
4-3