Block/ Wiring Diagram; Default Settings - ICP DAS USA tM-AD8C Quick Start Manual

8-channel isolated current analog input module

Advertisement

3. Block/ Wiring Diagram

 Use 26-12 AWG wire for signal connections.
 Strip the wire to a length of 7±0.5mm.
 Use a crimp terminal for wiring.
 Avoid high-voltage cables and power equipment as much as possible.
 For RS-485 communication, use insulated and twisted pair 24 AWG wire, e.g.
Belden 9841.

4. Default Settings

Default settings for the tM AD modules are as follows:
。 Protocol: Modbus RTU
。 Module Address: 01
。 Analog Input Type: type code 08, -10V to 10V
。 Baud Rate: 9600 bps
tM-AD8C 8-channel Current Analog Input Module- QuickStart (Jun/2016)