5 Commissioning
5.3
Basic information
The commissioning
procedure
24
Operating manual PxtFX active energy management device
V1.1DE/EN

Conditioning the PxtFX energy management device

• If the PxtFX energy management device has been de-energised for more than
1 year, it must be conditioned. Failure to do this may result in the PxtFX energy ma-
nagement device being damaged when the main supply voltage is switched on.
• The date of manufacture is on the model plate (
• During conditioning, the PxtFX energy management device is connected to the
DC link but is not ready for use.
Conditioning
time [h]
5
4
3
2
1
Fig. 15: Conditioning time, depending on the voltage-free period
Connect the PxtFX energy management device to the DC link
(
Chapter 5.2, page 17).
The PxtFX energy management device will be conditioned (charged up).
Wait for the duration of the conditioning period which corresponds to the length
of the voltage-free period (
The application can then be enabled again.
1
2
3
Voltage-free time [years]
Fig. 15).
Page 9, Fig. 5).
5
4