EACIE Evacuation Alert Control and Indicating Equipment
7.5.3
Fix Address Faults
This function helps to locate and fix devices with duplicate (double) addresses and also activates device
(polling) LEDs. Typically, a fault may have been displayed at the panel stating 'Duplicate Address'.
When the FIX ADDRESS FAULTS prompt is displayed press Accept. The panel will reinitialise and check the
loop, then find the double address and automatically fix the fault. No user interaction is required.
7.5.4
Verify Loop
This function restarts the loop and displays any loop configuration faults. This function may be used, for
example, if there is a problem with a missing device, or a device not closing its s/c isolator.
When selected, press Accept, select a loop number and the panel will power down the loop and then re-initialize
the loop devices.
7.5.5
Device Manager
At Access Level 3 > Commissioning Functions, press the
For ease of access, this is a duplicate of Device Manager under Engineering functions (see section 7.4.1 for
details).
7.5.6
Add New Device
This function may be used, for example, to replace a faulty loop device or add a new loop device.
When selected, press Accept, select the loop and device number then press Accept.
Replace or add the selected loop device.
If a device has been replaced the panel will auto address the new device at the selected loop and device number. If a
device has been added the panel will force a loop learn when exiting access level 3.
7.5.7
Add/Delete/Edit a Device
Refer to Device Manager section 7.4.1 for details.
Page 29 of 38 Approved Document No. DFU5030020 Rev 1 Installation and Programming Manual